![Rockwell Automation Allen-Bradley 140M User Manual Download Page 60](http://html.mh-extra.com/html/rockwell-automation/allen-bradley-140m/allen-bradley-140m_user-manual_1475383060.webp)
60
Rockwell Automation Publication 450L-UM001F-EN-P - March 2022
Chapter 5 System Configuration
4. As soon as the status indicator STS changes from green/red to green/off,
release the optical push button.
5. Release is indicated with a change of frequency of 10 Hz to 1 Hz (status
indicator STS green/off and a 50:50 duty cycle).
6. Within 2 seconds, actuate the optical push button.
7. Status indicator STS indicates the activation by a new green/red
frequency of 10 Hz and a 50% duty cycle.
8. Actuate the optical push button for 5 seconds.
9. As soon as the status indicator changes from green/red blinking to
green/off blinking, release.
10. After releasing, the status indicator STS is steady green.
If any error occurs in this procedure, the new configuration is not stored and
the STS-indicator starts blinking again (1 Hz, green/red, and 50:50 duty cycle).
For example:
•
If the actuator is released before the 5 seconds.
•
It is not actuated within the 2 seconds thereafter.
IMPORTANT
Once the configuration confirmation procedure is completed, verify
that the operating mode has changed to the intended configuration.