Electromagnetic Interference
6-7
Enclosure Lighting
Fluorescent lamps are also sources of EMI. If you must use fluorescent
lamps inside an enclosure, the following precautions may help guard against
EMI problems from this source as shown in the figure below:
•
install a shielding grid over the lamp
•
use shielded cable between the lamp and its switch
•
use a metal-encased switch
•
install a filter between the switch and the power line, or shield the
power-line cable
Filter
Shielding-grid
over lamp
Shielded
cable
Metel-encased
switch
Line-filter or
shielded
power line
ac power