A-6
Motor Cable Length Restrictions Tables
➊
Cable is Belden 295xx series or equivalent
NR = Not Recommended
NA = Not Available at time of printing
Table A.E 160 Drive, 480V
380-460V
Ratings
Motor
Insulation Rat-
ing
Motor Cable Only
RWR at Drive
Reactor at Motor
Shielded
➊
Unshielded
Shielded
➊
Unshielded
Shielded
➊
Unshielded
Volts
P-P
meters
feet
meters
feet
meters
feet
meters
feet
meters
feet
meters
feet
4.0 kW
(5 hp)
1000
13.7
45
6.1
20
160
525
183
600
99.1
325
91.5
300
1200 27.4
90
12.2
40
160
525
183
600
160
525
130
425
1600 160
525
145
475
160
525
183
600
160
525
183
600
2.2 kW
(3 hp)
1000 12.2
40
12.2
40
160
525
183
600
68.6
225
76.2
250
1200 27.4
90
18.3
60
160
525
183
600
99.1
325
130
425
1600 160
525
152
500
160
525
183
600
160
525
183
600
1.5 kW
(2 hp)
1000 12.2
40
12.2
40
130
425
183
600
99.1
325
91.5
300
1200 27.4
90
18.3
60
130
425
183
600
130
425
137
450
1600 152
500
152
500
130
425
183
600
165
540
183
600
0.75 kW
(1 hp)
1000 16.8
55
12.2
40
99.1
325
183
600
99.1
325
107
350
1200
38.1
125
18.3
60
99.1
325
183
600
152
500
137
450
1600 152
500
152
500
99.1
325
183
600
152
500
183
600
0.55 kW
(0.75 hp)
1000 13.7
45
12.2
40
91.5
300
183
600
91.5
300
91.5
300
1200 38.1
125
18.3
60
91.5
300
183
600
152
500
152
500
1600 152
500
152
500
91.5
300
183
600
152
500
183
600
0.37 kW
(0.5 hp)
1000 13.7
45
27.4
90
91.5
300
130
425
91.5
300
130
425
1200 38.1
125
54.9
180
91.5
300
130
425
152
500
152
500
1600 152
500
152
500
91.5
300
130
425
152
500
152
500
Summary of Contents for Allen-Bradley 1305-AA02A
Page 4: ...ii Summary of Changes Notes ...
Page 40: ...2 18 Power Distribution Notes ...
Page 48: ...3 8 Grounding Notes ...
Page 68: ...4 20 Practices Notes ...
Page 78: ...6 8 Electromagnetic Interference Notes ...
Page 94: ...Glossary 4 UL Underwriters Laboratories ...
Page 100: ...Index 6 ...
Page 101: ......