Power Distribution
2-7
Note:
Grouping multiple drives on one reactor is acceptable; however, the
reactor percent impedance must be large enough when evaluated for each
drive separately, not evaluated for all loads connected at once.
These recommendations are merely advisory and may not address all
situations. Site specific conditions must be considered to assure a quality
installation.
Table 2.A AC Line Impedance Recommendations for Bulletin 160 Drives
Table 2.B AC Line Impedance Recommendations for Bulletin 1305 Drives
Drive Catalog #
(1)
Volts
kW (hp)
Max Supply
KVA
(2)
3% Line
Reactor Open
Style 1321-
Reactor
Inductance (mh)
Reactor Current
Rating (Amps)
160-
AA02
240
0.37(0.5)
15
3R4-B
6.5
4
AA03
240
0.55 (0.75)
20
3R4-A
3
4
AA04
240
0.75 (1)
30
3R4-A
3
4
AA08
240
1.5 (2)
50
3R8-A
1.5
8
AA12
240
2.2 (3)
75
3R12-A
1.25
12
AA18
240
3.7 (5)
100
3R18-A
0.8
18
BA01
480
0.37(0.5)
15
3R2-B
20
2
BA02
480
0.55 (0.75)
20
3R2-A
12
2
BA03
480
0.75 (1)
30
3R2-A
12
2
BA04
480
1.5 (2)
50
3R4-B
6.5
4
BA06
480
2.2 (3)
75
3R8-B
3
8
BA10
480
3.7 (5)
100
3R18-B
1.5
18
(1)
Shaded rows identify drive ratings without built-in inductors
(2)
Maximum suggested KVA supply without consideration for additional inductance
Drive Catalog #
(1)
Volts
kW (hp)
Max Supply
KVA
(2)
3% Line
Reactor Open
Style 1321-
Reactor
Inductance (mh)
Reactor Current
Rating (Amps)
1305-
-AA02A
240
0.37(0.5)
15
3R4-A
3
4
-AA03A
240
0.55 (0.75)
20
3R4-A
4
4
-AA04A
240
0.75 (1)
30
3R8-A
1.5
8
-AA08A
240
1.5 (2)
50
3R8-A
1.5
8
-AA12A
240
2.2 (3)
75
3R18-A
0.8
18
-BA01A
480
0.37 (0.5)
15
3R2-B
20
2
-BA02A
480
0.55 (0.75)
20
3R2-B
20
2
-BA03A
480
0.75 (1)
30
3R4-B
6.5
4
-BA04A
480
1.5 (2)
50
3R4-B
6.5
4
-BA06A
480
2.2 (3)
75
3R8-B
3
8
-BA09A
480
3.7 (5)
100
3R18-B
1.5
18
(1)
Shaded rows identify drive ratings without built-in inductors
(2)
Maximum suggested KVA supply without consideration for additional inductance
Summary of Contents for Allen-Bradley 1305-AA02A
Page 4: ...ii Summary of Changes Notes ...
Page 40: ...2 18 Power Distribution Notes ...
Page 48: ...3 8 Grounding Notes ...
Page 68: ...4 20 Practices Notes ...
Page 78: ...6 8 Electromagnetic Interference Notes ...
Page 94: ...Glossary 4 UL Underwriters Laboratories ...
Page 100: ...Index 6 ...
Page 101: ......