1606-XLE240EP 24V, 10A; Single Phase Input
10000126343
(Version 00)
www.ab.com
Page 4
6.
I
NPUT
I
NRUSH
C
URRENT
An active inrush limitation circuitry limits the input inrush current after turn-on of the input voltage.
The charging current into EMI suppression capacitors is disregarded in the first milliseconds after switch-on.
AC 100V
AC 120V
AC 230V
Inrush
current
max. 10A
peak
10A
peak
10A
peak
-25°C to +70°C
typ. 3A
peak
3A
peak
3A
peak
-25°C to +70°C
Inrush
energy
typ. 1A
2
s 1A
2
s 1A
2
s
-25°C to +70°C
Fig. 6-1 Input inrush current, typical behavior
Input Current
Input Voltage
Output Voltage
A
A:
Start-up delay = Inrush delay
Input:
230Vac
Output: 24V, 10A
Ambient: 25°C
Upper curve:
Input current 10A / DIV
Medium curve:
Input voltage 500V / DIV
Lower curve:
Output voltage 20V / DIV
Time scale:
100ms / DIV
7.
H
OLD
-
UP
T
IME
AC 100V
AC 120V
AC 230V
Hold-up Time
typ.
62ms
107ms
92ms
typ. 23ms 46ms 42ms
typ. 17ms 35ms 33ms
Fig. 7-1 Hold-up time vs. input voltage
Fig. 7-2 Shut-down behavior, definitions
0
20
40
120ms
85
120
100
180
230Vac
Hold-up Time
80
60
100
Input Voltage
a) 24V 5A typ.
b) 24V 5A min.
c) 24V 10A typ.
d) 24V 10A min.
e) 24V 12A min.
a
a
b
c
c
d
d
e
e
b
- 5%
Hold-up Time
Zero Transition
Output
Voltage
Intput
Voltage
Note: At no load, the hold-up time can be up to several seconds. The green DC-ok lamp is on during this time.