1606-XLE240EP 24V, 10A; Single Phase Input
10000126343
(Version 00)
www.ab.com
Page 10
15.
E
NVIRONMENT
Operational temperature
-25°C to +70°C (-13°F to 158°F)
reduce output power according
Output de-rating
6W/°C
60-70°C (140°F to 158°F)
Storage temperature
-40 to +85°C (-40°F to 185°F)
storage and transportation
Humidity
5 to 95% r.H.
IEC 60068-2-30
Do not energize while condensation is present
Vibration sinusoidal
2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g
2 hours / axis
IEC 60068-2-6
Shock
30g 6ms, 20g 11ms
3 bumps / direction, 18 bumps in total
IEC 60068-2-27
Altitude
0 to 6000m (0 to 20 000ft)
Reduce output power or ambient temperature above
2000m sea level.
Output de-rating (for altitude)
15W/1000m or 5°C/1000m
above 2000m (6500ft), see
Over-voltage category
III
EN 50178, altitudes up to 2000m
II
Altitudes from 2000m to 6000m
Degree of pollution
2
EN 50178, not conductive
Fig. 15-1 Output current vs. ambient temp.,
Fig. 15-2 Output current vs. altitude, 24V
0
-25
0
20
40
70°C
2
4
6
8
10
12A
60
Ambient Temperature
continuous
short
term
Allowable Output
Current at 24V
0
0
2000
4000
6000m
2
4
6
8
10
12A
Altitude
A... Tamb < 60°C
B... Tamb < 50°C
C... Tamb < 40°C
C
B
A
short term
Allowable Output
Current at 24V
The ambient temperature is defined 2cm below the unit.
16.
P
ROTECTION
F
EATURES
Output protection
Electronically protected against overload, no-load and short-circuits
Output over-voltage protection
typ. 35Vdc
max. 39Vdc
In case of an internal power supply defect, a redundant circuitry limits
the maximum output voltage. The output shuts down and automatically
attempts to restart.
Output over-current protection
electronically limited
see
Degree of protection
IP 20
EN/IEC 60529
Penetration protection
> 3.5mm
e.g. screws, small parts
Over-temperature protection
yes
output shut-down with automatic restart
Input transient protection
MOV
Metal Oxide Varistor
Internal input fuse
T6.3A H.B.C.
not user replaceable
Note: In case of a protection event, audible noise may occur.