1606-XLE240EP 24V, 10A; Single Phase Input
10000126343
(Version 00)
www.ab.com
Page 5
8.
O
UTPUT
Output
voltage
nom. 24V
Adjustment
range
min. 24-28V
guaranteed
max.
30V
at clockwise end position of potentiometer
Factory
setting
24.1V
±0.2%,
at full load, cold unit
Line
regulation
max.
70mV
90 to 132Vac or 180 to 264Vac
Load
regulation
max.
100mV
static value, 0A
Æ
10A
Æ
0A
Ripple and noise voltage
max.
50mVpp
20Hz to 20MHz, 50Ohm
Output
capacitance
typ. 7
000µF
Output current
nom.
10A
nom.
12A
at 24V, max. 1 minute every 10 minutes in an average
nom.
8.6A
nom.
10.3A
at 28V, max. 1 minute every 10 minutes in an average
Output
power
nom.
240W
ambient < 60°C
nom.
288W
max. 1 minute every 10 minutes in an average
Short-circuit
current
min.
14A
load impedance 100mOhm, see
max.
18A
load impedance 100mOhm, see
Fig. 8-1 Output voltage vs. output current, typ.
Output Voltage
0
0
4
8
12
16
4
8
12
28V
16
20
24
20A
10
6
2
14
18
Adjustment
Range
Output Current
+60°C
+25°C
-25°C
Peak current capability (up to several ms)
The power supply can deliver a peak current which is higher than the specified short term current. This helps to start current demanding loads or to
safely operate subsequent circuit breakers.
The extra current is supplied by the output capacitors inside the power supply. During this event, the capacitors will be discharged and causes a voltage
dip on the output. Detailed curves can be found in chapter 25.1.
Peak current voltage dips
typ.
from 24V to 18.5V
at 20A for 50ms, resistive load
typ.
from 24V to 17.5V
at 50A for 2ms, resistive load
typ.
from 24V to 12V
at 50A for 5ms, resistive load