background image

9

Delivery

- The G100/20-30-40-50 and G100/20-30-40-50IE

boilers are delivered fully assembled in a single
package.

- The G100/70-90-110 and G100/70-90-110IE

boilers are delivered in four packages which
contain:
- Fully assembled boiler, burners and gas train

assembly.

- Outer casing.
- Smoke hood.
- Control panel

- The G100/GTA and G100IE/GTA boilers are

delivered in three packages which contain:
- Fully assembled G100 or G100 IE boiler.
- Storage cylinder.
- Cylinder casing and boiler support framework.

Installation

- Observe current regulations applicable with

regard to access to the boiler for future start-up
operations, monitoring and servicing.

- Ensure there is a 220/230V-50 Hz single- phase

earthed power point as well as a water supply
and a drain near the final installation location of
the boiler.

- It is advisable to install a non-thermosiphonic

valve in the ”heating flow” pipe to prevent the
radiators from warming up when there is no
demand for heating.

Assembly

Location

- Locate the boiler in accordance with the layout

and position of the Flow, Return and Gas inlet
pipes, flue duct, drain, etc.

- The boiler should be installed at least 0.5 m away

from any flammable material.

- If there is a wooden, cork, or similar heat-

sensitive floor, protect the supporting surface in
an area of 0.5 m around the boiler with 20 mm-
thick (minimum) glass fibre.

- The G100/70-90-110 and G100/70-90-110IE

boilers may only be installed outdoors
(protected) or in a room separate from the
inhabited rooms, suitably ventilated directly to
the outside air.

- For G100/GTA and G100IE/GTA boilers, ensure

there is enough room at the back so that future
water connections and the assembly of the
cylinder casing can be performed without
difficulty.

Boiler support framework, optional electric
heater and hydraulic unit (GTA version only)

- In the cylinder ”Return” tapping screw in the

1” x 3/4” reducing nipple (1), the 3/4” m-f elbow
(2), the check valve (3) -with the arrow pointing
towards the flexible tube adaptor- and finally
screw in the adaptor itself (4). 

Fig. 1

.

- Put the cylinder cradle in its final location, with

the angle irons (5) facing the viewer. 

Fig. 2

.

- Rest the cylinder on the cradle, with its metal

base facing the viewer and the prepared
assembly in the lower section, properly centred
and against the front supporting plate.

- Screw the 1/2” plug into the rear tapping on the

left-hand side of the cylinder (viewed from its
metal base) and the nipple (6) into the top
tapping.

- As an option, when required, insert the electric

heater element into the cylinder and screw it in
the plug tapping (7). Wire it to the terminals
marked on the wiring diagrams shown in the
Instructions that come with the relevant control
panel.

- Place the two vertical brackets (8), which are

identical, such that the hole which is closest to
the end of the top profile stays on the right, as
viewed from its metal base.

- Place the above vertical brackets behind the

angle irons (5) and fasten them by introducing
the M6 x 15 bolts (9) through the angle irons

by screwing them to the brackets. At the time
the brackets (8) are being screwed in, install the
tie- rods (1 0) – one on either side. 

Fig. 3

 and 

4

.

- Rest the boiler supporting base (11) on the

brackets (8) and secure it with the M6 x 15 bolts
(12) and nuts provided.

- Put the unpacked boiler and its support (’U’

shapes) (13) on the floor so that the U-shaped
profiles come into contact with the rear legs. The
rear left leg will coincide with the U-shape which
has a hole in the welded stop (14). 

Fig. 5

.

- Raise the back side of the boiler and slide the

support (13) under it until the U-shaped profiles
come into contact with the back side of the
boiler’s front legs.

- Raise the boiler through the front and slide it

over the U-shaped profiles until its rear legs
come into contact with the welded stops.

- Fasten the rear left leg of the boiler to the drilled

stop, using a nut and bolt. – Insert the rods of
both handles (15) into the end holes in the U-
shaped profiles of the boiler support (13) and
secure them with the nuts provided. 

Fig. 6

.

- Lift both the support (13) and the boiler through

the handles (15) and rest them on the boiler
supporting base (11). The front of the boiler
should face in the same direction as the metal
base of the cylinder, while the hex heads of the
bolts (12) that fasten the supporting base (11)
to the vertical brackets (8) should coincide with
the holes (16) in the boiler support (13). 

Figs. 4

and 

5

.

- Disassemble the handles (15) and keep them

for future use (for instance, under the cylinder).

- Fasten the support (13) to the supporting base

(11) with the four nuts and bolts provided.

- Screw the adaptor (4) onto the 500 mm flexible

tube union (17). 

Fig. 4

.

- Screw the cone piece (18) on the reducing T

(19). The side port should be horizontal and
facing out. 

Fig. 7

.

- Screw the nipple (20) to the elbow (21).
- Screw the elbow (21) to the side port of the

reducing T(19).

- Insert a 3/4” gasket into the union adaptor on

the ”Return connection” pipe (22) 

Fig. 4

 and

screw it to the elbow (21) through the slotted
hole in the supporting base (11).

- Place a 3/4” gasket between the 500 mm flexible

tube (17) and the nut on the ”Return connection”
pipe (22) and join them together.

- Fix the pipe (22) to the cylinder metal base with

the aid of the clamp (23) as shown in 

figure 4

.

- Screw the reducing nut (24) into the ”Flow”

tapping. 

Fig. 7

.

- Screw the nut (24) into an end of the ”boiler outlet

pipe” (25). The T with union should be facing
the floor.

- Install the safety valve. Where appropriate.
- Place a gasket in the vertical T union and screw

it to the pump. The arrow on the pump body
should point to the floor and the terminal box be
at the top.

- Screw the 520 mm flexible tube to the nipple (6)

on the cylinder through the hole provided in the
supporting base (11) and screw the union
adaptor on the other end of the flexible tube to
the pump, having put a gasket beforehand.

Watertight Test

For G100/70-90-110 and G100/70-90-110IE
boilers:
- Unscrew the non-return valve sensor (26) from

the control panel hydrometer and screw it into
the tapping in the front section. 

Fig. 8

.

- Fill the system with water and check the

hydraulic circuit for leaks.

In all boilers:
- Install the specific safety devices as shown in

Fig. 9

. The size of the safety conduits must

conform to the dimensions given for them in the
current Regulations.

- Install a drain cock in the tapping (27), or fit a

plug if the drain cock is located elsewhere; then
make the connection of the FLOW and RETURN
circuits, i.e. tappings (28) and (29)*

respectively. 

Fig. 10

.

* The assembled boilers have a 2” x 1” cone, while

G100/90-110 and G100/90-110IE are equipped
with a 2” x 2” distributor.

- With GTA version boilers, connect the cylinder

to the mains water supply and to the system
through the screwed nipples, observing their
destination as shown in 

Fig. 12

; then in the

”mains water inlet” connection before the
cylinder, install the Flexbrane safety unit in
accordance with the instructions that come with
it. Route the discharge to the general drain.

- Fill the system* with water and check the

hydraulic circuit for leaks.

* With GTA version boilers, it is essential to fill

the DHW circuit (storage cylinder) before the
heating circuit and, when appropriate, empty the
latter first.

Final Assembly

For G100/70-90-110 and G100/70-90-110IE:
- Rest the smoke hood (30) on the boiler and

secure it to the front and back sections by means
of the nuts and bolts provided. 

Fig. 8

.

- Place the insulating blanket over the boiler body

so that its ends overlap at the front of the boiler.

- Fasten the bracket-casing (31) to the front

section: with M8 x 10 screws through the top;
with M12 nuts and washers through the lower
right-hand side; and with MS nuts and washers
fasten it to he spacer which has been previously
screwed to the leg – through the lower left-hand
side. 

Fig. 11

.

- Fasten the side bracket (32) onto the bosses at

the top of the back section by means of M8 x 20
bolts. The angles should face inwards and the
slotted hole to the right. 

Fig. 10

.

- Secure the other side bracket (33) to the holes

in the back section cover using two M8 x 40
bolts. The angles should face inwards and the
slotted hole to the right.

- Temporarily hang the control panel from the

hooks (34) on the bracket casing (31). 

Fig. 11

.

- Insert the thermostat and thermometer probes

through the slotted hole (35) in the top left-hand
side of the bracket-casing (31).

- Screw the hydrometer sensor to the non- return

valve situated on the front section. – Insert the
thermometer, control (2 in the G100/90-110IE)
and safety limit thermostat(s) into the pocket in
the back section and fasten the capillaries with
the clip provided for this purpose. 

Fig. 12

.

- Remove the control panel from the casing

bracket hooks.

- Fix the casing side panels to the brackets (31),

(32) and (33) using the black Allen screws and
washers provided (four each).

- Rest the left-hand casing extension piece (36)

on its bottom side and secure it through the top
with a screw. 

Fig. 13

.

- Hang the control panel to the front of the casing

panels and secure it through the bottom with
the two screws provided.

In all boilers:
- Insert the end of the flue duct down into the

smokehood collar and ensure that the joint is
air-tight by applying pipe jointer material, ceramic
fibre gasket or putty which does not set hard.

- Connect the end of the boiler gas train to the

gas supply pipe and with soapy water check that
the gas train is air-tight.

Electrical connections

- In boilers which are delivered disassembled,

make the connection between the control panel
and the boiler gas valve by means of the
connectors situated at the bottom left hand-side
of the control panel and at the end of the valve
wiring.

- Wire the heating pump, the optional ambient

thermostat and the mains power supply to the
terminals marked on the wiring diagrams that
come with the Instructions for the control panel.
For boilers which are delivered fully assembled,
please note that before proceeding as indicated

GB

ATC 

ROC

Summary of Contents for G 100 IE

Page 1: ...INSTALLATEUR D Caldaie Istruzioni per l Installazione il Montaggio e il Funzionamento per l INSTALLATORE I Caldeiras Instruções de Instalação Montagem e Funcionamento para o INSTALADOR P Calderas Instrucciones de Instalación Montaje y Funcionamiento para el INSTALADOR E Chaudières Instructions d Installation de Montage et de Fonctionnement pour l INSTALLATEUR F A T C R O C ...

Page 2: ...la tubazione allo scarico Canalizar para o esgoto Gas Gaz Gás Retorno Return Retour Rückströmung Ritorno Retorno Instalación en circuito abierto Open vented installation Installation en circuit ouvert Montage des offenen Kreislaufes Impianto a circuito aperto Instalação em circuito aberto Ida Flow Départ Einlauf Mandata Ida Ida Flow Départ Einlauf Mandata Ida Tuberia expansión de seguridad Safety ...

Page 3: ...n Wiederumlauf Ricircolazione Recirculação Entrada agua de red Mains water sypply Entrée d eau du reseau Heiz und Leitungswasserzufluss Entrata acqua dalla rete Entrada água de rede Vaina Pocket Gaine Hülse Guaina Bainha Salida A C S DHW outlet Sortie E C S Heisswasserauslauf Uscita A C S Saída A Q S A T C R O C ...

Page 4: ...4 90 2 4 3 G100 40 G100 40IE 38 200 44 4 90 5 5 3 G100 50 G100 50IE 48 350 56 2 90 8 6 3 G100 70 G100 70IE 68 800 80 91 3 8 3 G100 90 G100 90IE 88 200 103 91 5 10 3 G100 110 G100 110IE 108 300 126 91 6 12 3 Caldera Boiler type Chaudière Heizkessel Caldaia Caldeira Potencia útil nominal Nominal Heat Output Puissance utile Nutzleistung Potenza utile nominale Potência útil nominal Rendimiento útil Ne...

Page 5: ... Caldera Boyler type Chaudière Heizkessel Caldaia Caldeira Cotas mm Dimensions mm Cotes mm Abmessungen mm Quote mm Cotas mm Gas Ciudad Town Gas Gaz de ville Stadgas Gas di Città Gas Cidade Gas Nat y GLP Nat Gas and LPG Gas Nat et GLP Erdgas und GLP Gas Nat e GLP Gas Nat GLP A B C D E F F g F H I g G100 20 G100 20 IE 850 800 110 127 551 651 3 4 ext 651 275 275 1 2 ext G100 30 G100 30 IE 850 918 113...

Page 6: ... 1 ext b Válvula seguridad 1 2 c Retorno 1 int d Desagüe 3 4 int g Conexión gas x Recirculación 3 4 y Entrada agua red 3 4 z Consumo 3 4 a Flow 1 ext b Safety valve 1 2 c Return 1 int d Drain 3 4 int g Gas connection x DHW recirculation 3 4 y Mains water inlet 3 4 z DHW outlet 3 4 a Aller 1 ext b Soupape de sécurité 1 2 c Retour 1 int d Drainage 3 4 int g Connexion gaz x Recirculation 3 4 y Entrée...

Page 7: ...24 I m para t 30 K Diámetro inyector quemador mm Size of burner injector mm Diamètre injecteur brûleur mm Durchmesser Brennerdüsen mm Diametro dell injecttore del bruciatore mm Diâmetro injector queimador mm Caldera Boiler type Chaudière Heizkessel Caldaia Caldeira G as natural Natural G as G as naturel Erdgas G as naturale G ás natural G LP LPG G LP G LP G LP G LP G as ciudad Town G as G az de vi...

Page 8: ... n h Quantité minimale d air ene m3 n h Minimale Luftmenge in e m3 n h Minima quantità d aria in e m3 n h Quantidade de ar mínima em e m3 n h Caldera Boiler type Chaudière Heizkessel Caldaia Caldeira G 20 G 25 G 30 G 31 Caldera Boiler type Chaudière Heizkessel Caldaia Caldeira G 110 G100 20 G100 20 IE 32 56 32 59 30 98 31 24 G100 20 30 62 G100 30 G100 30 IE 44 94 44 94 42 65 42 99 G100 30 42 31 G1...

Page 9: ...Insert a 3 4 gasket into the union adaptor on the Return connection pipe 22 Fig 4 and screw it to the elbow 21 through the slotted hole in the supporting base 11 Place a 3 4 gasket between the 500 mm flexible tube 17 and the nut on the Return connection pipe 22 and join them together Fix the pipe 22 to the cylinder metal base with the aid of the clamp 23 as shown in figure 4 Screw the reducing nut...

Page 10: ...osition of the above mentioned switches to isolate all power supply to the boiler Refer to the Instructions for the Control Panel Press the knob or lever 15 right down for 10 seconds and follow the lighting up operations described in steps 3 4 8 9 and 10 or to stop it as explained in the previous paragraphs Figs 15 16 and 17 First lighting of G100 GTA boilers DHW only with electric heater Control ...

Page 11: ...er to the system wait until the boiler is completely cold before doing so Flue limit thermostat for the products of combustion G100 20 to 50 G100 GTA G100 20 to 50IE and G100IE GTA boilers The boiler incorporates a safety system which detects an inadequate evacuation of flue gases It includes a thermostat which is triggered when overheated flue gases go through the draught diverter thus causing th...

Reviews: