Electrical installer
Installation, use and maintenance manual – GAHP-AR
27
4
Table 4.1
CAN bus cables type
CABLE NAME
SIGNALS / COLOR
MAX LENGTH
Note
Robur
Ordering Code MCVO008
ROBUR NETBUS
H= BLACK
L= WHITE
GND= BROWN
1475 ft
Honeywell SDS 1620
In all cases the fourth conductor should not be
used
BELDEN 3086A
H= BLACK
L= WHITE
GND= BROWN
1475 ft
TURCK type 530
DeviceNet Mid Cable
TURCK type 5711
H= BLUE
L= WHITE
GND= BLACK
1475 ft
Honeywell SDS 2022
TURCK type 531
H= BLACK
L= WHITE
GND= BROWN
656 ft
GND is the common signal wire, and not a ground con-
nection.
How to connect the CAN bus cable to the appliance
To connect the CAN bus cable to the S61 electronic board
(Paragraph 1.5
p. 12), located in the electrical panel inside the
unit, (Figure 4.2
1.
Access the electrical board of the appliance according to the
Procedure 4.2
2.
Connect the CAN bus cable to the GND (shielding/ground-
ing) + L and H terminals (two signal wires).
3.
Place the CLOSED J1 Jumpers (Detail A) if the node is ter-
minal (one connected CAN bus cable section only), or OPEN
(Detail B) if the node is intermediate (two connected CAN
bus cable sections).
4.
Connect the DDC to the CAN bus cable according to the in-
structions of the following Paragraphs and DDC Manual.
Figure 4.2
Connection of the CAN bus cable to the electronic board
SCH
Electronic board
GND
Common data
L
Data signal LOW
H
Data signal HIGH
J1
Jumper CAN bus in board
A
detail of "terminal node" case (3 wires; J1 = jumper "closed")
B
Detail of "intermediate node" case (6 wires; J1 = jumper "open")
P8
CAN port/connector
GAHP Configuration (S61) + DDC
System (1) see also Paragraph 1.6
Figure 4.3
CAN bus connection for systems with one unit
DDC
Direct Digital Control
SCH
S61 controller
J1
Jumper CAN bus in board
J21
Jumpers CAN bus on DDC board
H,L,GND Data signal wires (ref. cables table)
A
Terminal node connection (3 wires; J1 and
J21 = "closed")
B
CAN bus cable shield
C
Insulating tape to protect the shield of the
CAN bus cable
D
Eyelet terminal and fixing screw
F2
5
2
PUMP
230V
N
J10
CONTACT
BK WHBR
FAN
L
NO
L N
230V
MAIN
N L
BOX
IGN.
3
6
W
R
Y
F4
0
F3
F1
24ac2
0 V
1
4
JP11
FL
24 ac1
TL
TA2
TCN
THMFTHRF
TG
TA
TA1
JTAG
SRT2
SRT1
JP12
A2
P6
TF
A1
GND
SP1
H
L
P8
GND
JUMPER J1
A
GND
H L
JUMPER J21
P8
P8
SCH
H
L
GND
6
5
1 23 4
4
3
2
1
DDC
L H
A
B
C
D
Summary of Contents for GAHP-AR