Installation and user manual
Error! Use the Home tab to apply
Titolo 1 to the text that you want to
appear here.
36
Technical data
CALDARIA CONDENSING
100
Gas category
II2H3+
Boiler type (EN 297)
B 23 (C 63,C63
X
)
Burners x nominal heat input (Hs)
2 x 50
Max/min water pressure
Bar
6 / 0.5
Power supply
V
230 V
Nominal heat input ( HS )
kW
16
100
Nominal heat input ( Hi )
kW
14.4
89.9
Nominal heat output 100% (80 - 60° C)
kW
88.30
Nominal heat output 100% (50 - 30° C)
kW
96.80
Nominal heat output 100% (60 - 40° C)
kW
95.40
Max. condensate production - 100% (50 - 30° C)
G20 gas
Kg/h
14.4
Efficiency (Hi ) (Directive 92/42/CEE)
Efficiency at full load (80 - 60° C)
%
98.2
Efficiency at full load (50 - 30° C)
%
107.7
Efficiency at full load Tm = 50° C (60 - 40° C)
%
106.1
Efficiency at reduced load 30% (80 - 60° C)
%
98.7
Efficiency at reduced load 30% (50 - 30° C)
%
108.7
Efficiency at reduced load 30% Tm = 50° C (60 -
40° C)
%
106.6
Combustion efficiency (80 - 60° C ; Ta = 20° C)
%
98.7
Energy lost with burner ON (80 - 60° C)
Pf
%
1.3
Energy lost with burner OFF (80 - 60° C)
Pubs
%
0.1
Energy lost by the shell (Tm = 70° C)
%
0.5
Flue temperature
° C
Temp. 2.5° C (max 80° C)
Heating temperature regulation (min / max)
° C
20
80
Gas consumption (G20) (min / nominal)
m
3
/h
1.52
9.53
Pollutants in exhaust gas
Carbon monoxide CO (0% O
2
) (P min
P max)
ppm
10
80
Nitrogen oxide Kn
ox
class (ref EN 297)
5
Power
supply data
Power supply
V
230
Frequency
Hz
50
Maximum electrical power
W
333
Weight and dimensions
Height
mm
1000
Width
mm
600
Depth
mm
380
Empty weight
kg
90
Manifolds diameters
Flow water pipe
in
1” M
Inlet gas pipe
in
¾” M
Water return pipe
in
G ¾” M
Flue manifold
n°/mm
2x50
Summary of Contents for CALDARIA CONDENSING 100