10  Error list 

In  the  following  tables  are  listed  the  Caldaria  Condensing  100  series    errors.  If  the  error  is  a  type 

“A”  the 

“RESET” button needs to be pressed after eliminating the reason for the failure. If it is an error type “E”, the 
boiler will go back to normal operation, with no need to press the “RESET” button, once the reason for the 
failure has been eliminated.  

10.1  Master board error 

ERROR 

DESCRIPTION 

  ERROR 

DESCRIPTION 

A16 

Internal error 

  E02 

Flow probe open 

A18 

Internal error 

  E04 

Tank probe open 

A20 

Internal error 

  E18 

Flow probe shorted 

 

 

  E20 

Tank probe shorted 

 

 

  E23 

Internal error 

 

 

  E24 

Internal error 

 

 

  E25 

Internal error 

 

 

  E26 

Internal error 

 

 

  E32 

No_slaves_present 

 

 

  E34 

50hz_error 

 

10.2  Slave board error 

ERROR 

DESCRIPTION 

  ERROR 

DESCRIPTION 

A01 

Five unsuccessful ignitions attempts  

  E33 

 

Live and neutral reversed error (ni) 

A02 

Several unsuccessful attempts for flame 
ionization problems

 

  E34 

Reset button error. It has been 
pressed more than 7 times in a 30 
min interval 

A04 

Limit thermostat cut off water side (>90°C)

 

  E35 

Low water flow or low system pressure 
(<0.5 bar)

 

A05 

Gas valve coil cut off. 
Gas valve connector false contact.  
Defective gas valve connector. 
Limit thermostat intervention (>90°C) while burner 
was on. 

 

E36 

Internal error 

A06 

Missing or poor grounding

 

  E37 

Flame detection error

 

A07 

Internal hardware error 

  E38 

Shorted flue gas sensor 

A08 

Internal hardware error 

  E39 

Flue sensor with open contact

 

A09 

50hz_error 

  E40 

50 hz error 

A10 

Internal hardware error 

  E41 

Internal error 

A11 

Internal software error 

  E42 

Shorted flow sensor error 

A12 

Internal hardware error 

  E43 

Open flow sensor error 

A16 

The contact ot limit thermostat is open with burner 
off

 

  E44 

Shorted return sensor error 

A17 

Flow sensor error for excessive limit temperature

 

  E45 

Open return sensor error 

A18 

Return sensor error for exceeding the limit 
temperature 

 

E46 

Flow sensor error above 
max_flow_temperature 

A19 

The flue sensor intervened for over temperature 
>80°C.( In this case the fan operates at max 
speed) 

 

E47 

Return sensor error above 
max_return_temperature 

A20 

Flame out too late after closing gas valve 

 

E48 

Flue sensor error above 
max_flue_gas_temperature 
(in this error the fan is on at full 
speed). 

A21 

Internal error 

  E49 

Missing or poor grounding

 

A22 

The slave had a type “E” error for more than 24 
hours

 

   

 

A23 

Internal error of the clock 

   

 

A24 

Fan error.  

   

 

A25 

Internal error 

   

 

 

Summary of Contents for CALDARIA CONDENSING 100

Page 1: ...D LBR571 rev B 15 MCM SDC 006 CALDARIA CONDENSING 100 Instruction manual Installation and use 92 42 CEE UNI EN ISO 9001 2000 UNI EN ISO 14001 2004...

Page 2: ...Power supply 15 5 2 Warnings 16 5 3 Electrical connections 16 5 3 1 5 3 1 Connection to temperature regulation devices 16 5 3 2 Antifreeze protection 16 5 3 3 Pump connection 16 5 3 4 Room Thermostat...

Page 3: ...erature not exceeding 110 C UNI 10845 Italian standard for flue gas venting system for hot water boilers fired with gaseous fuels The company Robur S p A has the certification UNI EN ISO 9001 2000 CAL...

Page 4: ...ing system and system for the production of sanitary hot water with accumulation simultaneously managing three different systems operating at three different temperatures Caldaria Condensing 100 is fi...

Page 5: ...ers Standard condensate discharge system in the boiler Fast connection of water condensate and gas optional collectors with right and left outlet Various thermal modules and the Master control station...

Page 6: ...t the point of sale where the product was purchased NUM DESCRIPTION 1 Packing 2 Product plate 3 Information about model gas type 4 Information about EC mark symbols 5 Lower support structure in polyst...

Page 7: ...ion 3 2 2 Wall mounting WARNING Thermal assemblies Caldaria Condensing 100 series could be installed outdoor 3 2 2 Wall mounting The boiler must be installed on a solid masonry wall by means of hooks...

Page 8: ...plate that is inside the shell It s important to verify the real match between available gas type and the type required by the boiler If your gas is a LPG it s important to verify the regulation of th...

Page 9: ...aldaria Condensing 100 installed in series can be realized with the installation of a polypropylene manifold it s optional with a diameter of 125 mm with male female connections The collector was conc...

Page 10: ...gs The condensate water produced by thermal assembly Caldaria Condensing 100 during its normal operation shall be discharged at atmospheric pressure i e by dripping into a siphon shaped container conn...

Page 11: ...delivery 1 M in Figure 6 System return 1 R in Figure 6 To create the hydraulic connection two kits are available the first one can be used for the installation of one Caldaria Condensing 100 the seco...

Page 12: ...perating pressure is 0 5 bar Each unit has a safety valve at 5 5 bar 3 7 2 Filling and emptying The boiler should be filled connecting the water network to any system point The boiler should be emptie...

Page 13: ...hown in Figure 19 it is necessary to calculate the three pumps for high temperature low temperature and sanitary hot water to guarantee in any case an adequate flow for each circuit and for each unit...

Page 14: ...Installation and user manual Error Use the Home tab to apply Titolo 1 to the text that you want to appear here 14 Figure 19 Figure 20...

Page 15: ...lue for the pressure drop 0 100 200 300 400 500 600 700 800 0 x n 500 x n 1000 x n 1500 x n 2000 x n 2500 x n 3000 x n l h mbar Figure 22 We have to remember that the pump has to supply 2000 l h with...

Page 16: ...the power supply cable break switch off the thermal assembly To replace it contact qualified personnel 5 3 Electrical connections 5 3 1 5 3 1 Connection to temperature regulation devices Caldaria Con...

Page 17: ...Sanitary temperature probe S2 J11 5 6 Flow temperature probe Low SE J11 7 8 External temperature probe T1 J12 9 10 Room thermostat High T2 J12 11 12 Room thermostat Low AI J12 13 14 Analogical device...

Page 18: ...tion of an alarm device A 220 V clear contact block output on the boiler s terminal strip allows to connect an outside sound or visual alarm device capable of highlighting any technical anomalies The...

Page 19: ...ery installation On of the many functions included in Caldaria Condensing 100 electronics allows for the installation of several modules in series to create thermal assemblies having an overall power...

Page 20: ...ase a value S5 Decrement It is necessary to decrease a value S6 Prog OK It is necessary to store a value U2 Luminous display Display information about boiler condition U3 Luminous display Display info...

Page 21: ...atus e g pump not functioning e g pump functioning P 1 0 P 1 1 10 Sanitary circuit pump status e g pump not functioning e g pump functioning P 2 0 P 2 1 11 Secondary pump status e g pump not functioni...

Page 22: ...he display returns to the parameters display mode and the T6 is displayed 6 40 If no procedures are carried out for 10 seconds after that S2 SET ESC has been pressed to modify the set point of the cor...

Page 23: ...C 1 70 5 To exit monitor mode press S2 SET ESC If no procedures are carried out for 5 minutes the boards automatically returns to functioning display 1 80 Trough S3 S3 arrow the following values can b...

Page 24: ...s overall length over 15 metres 7 1 2 Operating instruction 1 Shut any electric supply 2 Close the gas valve 3 Unscrew the two screws to remove the frontal panel 4 Remove the 3 screw from the gas val...

Page 25: ...he maximum power and then change if it s necessary the Venturi regulation 7 Let the boiler arrive to the minimum power by using S5 key 8 On left of the display it will appear a L Low minimum power act...

Page 26: ...ration of a battery with seven burner in cascade In case two blocks are present in an installation having a battery of seven burners i e seven slaves the first is made of 4 burners and the second is m...

Page 27: ...s homologated for safety performances and with a double processor technology Such device allows to continually control both flow temperature and the Dt between flow and return of the battery element M...

Page 28: ...NTC sensor 2 Storage heater with NTC sensor 5 Instant with flow switch 6 Storage heater with thermostat 7 P_dhw_max 1 255 230 Setting the max fan speed for dhw mode 8 T_Dhw_limit 10 C T_Dhw_max 60 Thi...

Page 29: ...1 Attenuation_high 0 C 70 C 0 The Tset is decreased with the attenuation function only if High Temperature thermostat input is open 0 The system is turned off after thermostat opening 1 n The set poin...

Page 30: ...If it is 0 it is used as the system pump 35 T4 frost protection 30 C 15 C 3 Temperature for starting frost protection on T4 If T4 this value or T1 5 C then the pump start If after 10 minutes T1 is not...

Page 31: ...y Titolo 1 to the text that you want to appear here 31 restored EXCEPT GAS TYPE NUMBER par 42 and par 43 settings 42 Flow switch present on the slaves 0 1 1 0 The slave check not for the flow switch 4...

Page 32: ...on 1 15 Max vel ventil max fan speed 230 16 Priorit riscald CH priority 0 17 Temp max CH1 80 18 Temp min CH1 50 19 Diff on CH1 CH1 on hyst 7 20 Diff off CH1 CH1 off hyst 3 21 Attenuaz CH1 CH1attenuati...

Page 33: ...ow water flow or low system pressure 0 5 bar A05 Gas valve coil cut off Gas valve connector false contact Defective gas valve connector Limit thermostat intervention 90 C while burner was on E36 Inter...

Page 34: ...Installation and user manual Error Use the Home tab to apply Titolo 1 to the text that you want to appear here 34 11 Electrical wiring diagram...

Page 35: ...Installation and user manual Error Use the Home tab to apply Titolo 1 to the text that you want to appear here 35...

Page 36: ...full load Tm 50 C 60 40 C 106 1 Efficiency at reduced load 30 80 60 C 98 7 Efficiency at reduced load 30 50 30 C 108 7 Efficiency at reduced load 30 Tm 50 C 60 40 C 106 6 Combustion efficiency 80 60...

Page 37: ...Installation and user manual Error Use the Home tab to apply Titolo 1 to the text that you want to appear here 37 Condensate pipe mm 18...

Page 38: ...Installation and user manual...

Page 39: ...Installation and user manual ROBUR S p A Via Parigi 4 6 24040 Verdellino BG Tel 39 035 888 111 Fax 39 035 4821334 info robur it www robur com...

Reviews: