Electrical installer
Installation, use and maintenance manual – Caldaria Con export
33
4
Figure 4.7
Connection of DHW diverter valve
VD Buffer tank diverter valve for DHW charging
M14 connector:
8
phase (DHW position)
9
neutral (common)
10 phase (heating position)
11
10
9
8
7
M4
M8
4
5
6
VD
ma
ce
ne
4.5.2
Connection of OCDS011 DHW buffer tank
probe
The SB buffer tank probe (optional OSND011) must be connect-
ed to terminals 34-35 of the electronic board (master board for
Caldaria 100.2), removing the electric resistance fitted as stand-
ard (Figure 4.8
p. 33).
The DHW buffer tank probe must be used as an alternative to the
DHW buffer tank thermostat (Paragraph 4.5.3
The supplied cable length is 3 meters.
If a longer length is required, a 2x0,75 mm² shielded cable with a
maximum length of 50 metres must be used.
For further information, refer to the documentation sup-
plied with the DHW buffer tank probe OSND011.
Figure 4.8
Connection of OCDS011 DHW buffer tank probe
SB DHW buffer tank probe OSND011
M9
SB
32
33
34
35
36
37
4.5.3
Connection of DHW buffer tank thermostat
The TB DHW buffer tank thermostat must be connected to ter-
minals 42-43 (connector M12) of the electronic board (master
board for Caldaria 100.2) (Figure 4.9
p. 33).
The DHW buffer tank thermostat must be used as an alternative
to the DHW buffer tank probe (Paragraph 4.5.2
The cable may not be longer than 50 metres, with a minimum
cable cross-section of 0,5 mm
2
.
Figure 4.9
Connection of DHW buffer tank thermostat
TB DHW thermostat (alternative to DHW buffer tank probe)
M12
38
51
52
53
M13
TB
39
40
41
42
43
44