First start-up
40
5
P26 (3)
Modbus address
Not used
-
1
Do not modify
P27 (3)
Modbus communication baud rate
Not used
-
0
Do not modify
P28 (3)
Modbus mode
Not used
-
2
Do not modify
P29
Post-circulation heating Δt
It is possible to set the temperature difference from the main burner shut down due
to the room thermostat, below which the pump is deactivated for the heating service.
0 ÷ 25
0
Value in °C
P30
Post-circulation DHW Δt
It is possible to set the temperature difference from the deactivation of the DHW
request to the pump deactivation for the DHW service.
0 ÷ 25
10
Value in °C
P31
Heating antifreeze temperature setting
It is possible to set the temperature of the water in the heating system at which the
antifreeze protection is activated.
5 ÷ 12
12
Value in °C
P32
Flowmeter enable
Not used
-
0
Do not modify
P33
Minimum water flow setting
Not used
-
28
Do not modify
P34
Activation of the auxiliary relay on the SVZ additional board
Not used
-
0
Do not modify
P35
Water flow control enable during start-up
It allows the verification, at each switch on, of the correct operation of the circulator.
0 ÷ 1
1
0 = disabled
1 = enabled
1. In presence of cascade controller ODSP039 (optional), if
DHW production is managed by the controller itself, param-
eter P01 must be set to value 0. Parameters P15, P21, P25 will
be inhibited as they are managed directly by the controller.
2. By setting a value of parameter P01 other than 5 (heating on-
ly), the parameters relating to DHW production, i.e. P09, P10,
P11, P15, P21, P25, P30 and the DHW antifreeze functions,
DHW probe error and diverter valve anti-locking are enabled.
3. Parameters P26, P27, P28 relating to Modbus settings must
be configured only in the presence of the cascade controller
ODSP039 (optional), following the instructions provided in
the manual supplied with the controller itself.
5.4.3
Caldaria 100.2
Table 5.3
Caldaria 100.2 electronic board parameters
Parameter Description
Range
Default
Setting
P00 (1)
Boiler model selection
0 ÷ 3
3
3 = 55 kW
P01 (2) (3) Boiler type selection
0 ÷ 2
1
0 = heating and storage DHW (the
DHW management mode is specified
in parameter P32)
1 = heating only
2 = do not use
P02
Gas type selection
WARNING: before changing the parameter value, read the instructions in Paragraph
5.6
0 ÷ 1
0
0 = G20, G25, G25.3
1 = LPG, G30, G31
P03
Heating temperature setting
0 ÷ 1
0
0 = standard (30÷80 °C)
1 = reduced (25÷45 °C)
P04
Heating run-up
It is possible to set the time, during the start-up phase, that the boiler takes to reach
the maximum set power (for the space heating service).
0 ÷ 5
3
0 = disabled
1 = 50 s
2 = 100 s
3 = 200 s
4 = 400 s
5 = 600 s
P05
Primary ignition time of a single unit
Time for which a single unit becomes primary at startup, after which the automatic
changeover with the other unit takes place.
0 ÷ 255
50
Value in hours
P06
Switching off a single unit
1 ÷ 3
3
1 = only master on
2 = only slave on
3 = both on
P07
Heating timing
You can set the minimum time in which the burner is kept off once the heating
temperature has reached the setpoint.
0 ÷ 90
36
Value in multiples of 5 s (default 36 x
5 = 180 s)
P08
Post-circulation heating timing
It is possible to set the operating time of the pump, in heating mode, after the main
burner has been switched off due to the intervention of the room thermostat.
0 ÷ 90
36
Value in multiples of 5 s (default 36 x
5 = 180 s)
P09 (2)
Post-circulation DHW timing
It is possible to set the operating time of the pump, for the DHW service, after the
setpoint in the DHW buffer tank has been reached.
0 ÷ 90
18
Value in multiples of 5 s (default 18 x
5 = 90 s)