Installation, user and maintenance manual
– AY Condensing line, AY series
45
Make sure the ground cable is longer than the live cables. In this way it will be the
last wire to be pulled away if the mains cable should accidentally be pulled, and will
thus guarantee the ground connection. Do not use gas pipes to ground electrical
appliances.
A wiring error, as well as impeding the correct operation of the appliance, could also
damage the electrical apparatus that it contains.
MULTIPLE APPLIANCE PLANTS
The appliance must be connected to a 230 V 1N - 50 Hz power supply, as follows (see
example in Figure 5.4 connection to electrical mains (230 V 1N - 50 Hz)
→
45):
You will need: the appliances hydraulically connected; the external electrical panel
configured by the installation technician. Necessary equipment and materials.
Make sure that the electrical panel configured by the technician is equipped with a 2
pole circuit breaker with minimum air gap of 3 mm, and two type T fuses of suitable
rating.
On each appliance, remove the front panel and open the electrical panel by re-
1.
moving the bolts securing it.
For each appliance, provide a FG7(O)R 3Gx1.5 type cable.
2.
Locate terminal block "MC" inside the panel of each appliance and hook up as
3.
shown in the figure.
On completion, restore the appliances to their fully assembled condition.
4.
The insertion of relays or other electrical components inside the General Electrical Pa-
nel of the appliance is not permitted. Do not activate the appliance if the hydraulic
plant has not been filled.
Figure 5�4 – connection to electrical mains (230 V 1N - 50 Hz)
Example of connection of more than one appliance to the mains.
LEGEND
MC
power terminal block
GS
Master 2-pole power switch
F
Fuse/s
N
Neutral terminal
Ground ground terminal
L
single-phase line terminal