Heating engineer
Installation, use and maintenance manual – G gas unit heater
21
3
Table 3.12
Data for the calculation of the air/fumes system with Ø 80/110/130 pipes available as optional
G30
G45
G60
G100
Flue gas exhaust pressure drop
Ø 80 mm
Pipe
1 m
Pa
2,8
5,9
9,3
22,4
Elbow
90°
Pa
3,6
7,8
12,7
31,6
Tee
Pa
8,5
17,7
27,9
67,2
Ø 110 mm
Pipe
1 m
Pa
0,6
1,2
1,9
4,6
Elbow
90°
Pa
1,0
2,2
3,5
8,6
Tee
Pa
1,8
3,7
5,8
13,8
Ø 130 mm
Pipe
1 m
Pa
0,3
0,5
0,9
2,0
Elbow
90°
Pa
0,5
1,1
1,8
4,4
Tee
Pa
0,8
1,6
2,6
6,1
Air intake pressure drop
Ø 80 mm
Pipe
1 m
Pa
1,0
2,0
3,2
7,5
Elbow
90°
Pa
1,4
3,0
4,9
12,3
Tee
Pa
2,9
6,1
9,5
22,6
Ø 110 mm
Pipe
1 m
Pa
0,2
0,4
0,7
1,6
Elbow
90°
Pa
0,4
0,8
1,4
3,4
Tee
Pa
0,6
1,3
2,0
4,7
Ø 130 mm
Pipe
1 m
Pa
0,1
0,2
0,3
0,7
Elbow
90°
Pa
0,2
0,4
0,7
1,7
Tee
Pa
0,3
0,6
0,9
2,1
Table 3.13
Data for the calculation of the air/fumes system with Ø 100 pipes
G30
G45
G60
G100
Flue gas exhaust pressure drop
Ø 100 mm
Pipe
1 m
Pa
0,9
1,9
3,0
7,1
Elbow
90°
Pa
1,4
3,1
4,9
12,3
Tee
Pa
2,8
5,7
9,0
21,2
Air intake pressure drop
Ø 100 mm
Pipe
1 m
Pa
0,3
0,7
1,0
2,4
Elbow
90°
Pa
0,5
1,2
2,0
4,9
Tee
Pa
1,0
2,0
3,1
7,3
Table 3.14
Data for the calculation of the air/fumes system with coaxial pipes available as optional
G30
G45
G60
G100
Coaxial exhaust pipe pressure drop
Ø 80/125 mm
wall
Pa
21,2
40,3
60,8
132,4
roof
Pa
23,8
50,5
-
Ø 130/180
mm
wall (1)
Pa
14,0
22,4
31,2
60,8
Ø 100/150
mm
roof
Pa
9,7
21,3
35,3
90,5
Ø 130/210
mm
roof
Pa
3,6
7,8
12,7
31,6
(1) Can be used only with OSTF009 support bracket
In the case of horizontal flue gas exhaust pipes in-
stallations, the following instructions must be ob-
served:
Length of the flue pipe < 1 m: install the flue pipe
with a counter slope of 2 or 3 cm towards the gas
unit heater (Figure 3.7
Length of the flue pipe > 1,5 m: the condensate
produced by the exhaust duct must be properly
collected and drained by a suitable discharge sys-
tem, in accordance with the applicable regulations
in force.
If vertical flue gas exhaust pipes longer than 1,5 m
are installed, at the base of the vertically mounted
flue gas exhaust pipe a T-shaped piece must be
fitted to collect the condensate, to prevent any
condensate drops from entering the gas unit
heater (Figure 3.2
p. 19).
For each 45° elbow an increment of 1,2 m in length
should be added.