Installation, use and maintenance manual – G gas unit heater
19
3
3.3.3.2
B23 type installation with roof flue gas exhaust
pipe
Figure 3.2
B23 type installation with roof flue gas exhaust pipe
Table 3.3
B23 type maximum allowed length with roof flue gas
exhaust pipe
Indicative maximum lengths (m)
Flue gas exhaust pipe
Ø 80
Ø 100
Ø 110
G30
20
30
30
G45
13
30
30
G60
9
30
30
G100
5
18
28
3.3.3.3
C13 type installation with separate ducts
Figure 3.3
C13 type installation with separate ducts
A View from above
1
Flue gas exhaust
2
Combustion air inlet
A
1 2
Table 3.4
C13 type maximum allowed length with separate
ducts
Indicative maximum lengths (m)
Air pipe
Flue gas exhaust pipe
Ø 80
Ø 100
Ø 110
Ø 80
Ø 100
Ø 110
G30
17
30
30
17
30
30
G45
12
30
30
12
30
30
G60
9
30
30
9
30
30
G100
6
21
20
6
21
20
3.3.3.4
C13 type installation with wall coaxial terminal
Figure 3.4
C13 type installation with wall coaxial terminal
A View from above
A
Table 3.5
C13 type maximum allowed length with 80/125 wall
coaxial terminal and Ø 80 ducts
Indicative maximum lengths (m)
Air pipe
Flue gas exhaust pipe
G30
11
11
G45
7
7
G60
4
4
G100
2
2
Table 3.6
C13 type maximum allowed length with 130/180 wall
coaxial terminal
Indicative maximum lengths (m)
Air pipe
Flue gas exhaust pipe
Ø 80
Ø 130
Ø 80
Ø 130
G30
13
30
13
30
G45
9
30
9
30
G60
6
30
6
30
G100
4
30
4
30
3.3.3.5
C33 type installation with roof coaxial terminal
Figure 3.5
C33 type installation with roof coaxial terminal