Page 62
10.3
Gas Valves - Automatic Ignition
The valve used for this range of heaters is the S.I.T. Nova gas valve.
10.3.1
Nova Range Valves
Nova range main valves may be converted to operate with or without a burner gas pressure regulator.
To convert Nova valve from Natural Gas to L.P.G. (see Fig 10.2)
i)
Remove the cover of the pressure regulator.
ii)
Completely unscrew the regulator adjusting screw and remove it complete with its spring.
iii)
Replace the adjusting screw and original cover with the blanking nut attachment.
This device screws fully into the body of the regulator until it stops and puts the regulator out of
action. The step opening feature of the main valve will still operate.
To Convert Nova Valve from L.P.G. to Natural Gas
Reverse the instructions above.
Fig 10.2 Conversion of Nova Family Valve
Blanking screw
For L.P.G.
Governor spring
assembly
Pressure regulator
Access cover
Pilot gas outlet
of valve
Blanked off
230 v electrical
connection
Gas outlet to
burner
Burner
pressure
test point
Inlet pressure
rest point
Gas inlet
Summary of Contents for Dualair DA260G Series
Page 2: ...Details of condense drain for cooling coil ...
Page 9: ...Page 7 Fig 2 2 DualAir 380 Module Dimensions FRONT VIEW REAR VIEW SIDE VIEW ...
Page 34: ...Page 32 Fig 5 2 Wiring for DualAir Units On Off Burner 24v Controls ...
Page 35: ...Page 33 Fig 5 3 Wiring for DualAir Units Hi Low Burner 230v Controls ...
Page 36: ...Page 34 Fig 5 4 Wiring for DualAir Units Hi Low Burner 24v Controls ...
Page 37: ...Page 35 Fig 5 6 Wiring for DualAir Units BMS Burner Modulation 230v Controls ...
Page 38: ...Page 36 Fig 5 7 Wiring for DualAir Units BMS Burner Modulation 24v Controls ...
Page 39: ...Page 37 Fig 5 7 Wiring for DualAir Units Full Burner Modulation 230v Controls ...
Page 40: ...Page 38 Fig 5 8 Wiring for DualAir Units Full Burner Modulation 24v Controls ...
Page 41: ......
Page 42: ......
Page 43: ......
Page 44: ......
Page 45: ......
Page 46: ......
Page 47: ......
Page 48: ......
Page 49: ......
Page 50: ......