Page 3
Section 1. General Specification - DualAir® Unit
1.1
Basic Information
1.1.2
Description
The DualAir® combined heating and cooling unit is formed by four sections combined into a single
unit and delivered as a complete assembly ready for installation on site. The DualAir® unit is designed
to be installed with the air flow from right to left as shown in Fig 1.1. Units with opposite air flow
direction are available by special order.
The four sections are as follows:-
1.1.3
Gas Fired Heater Section
The heater section is a CUHD/A 300 or the CUHD/A 380 automatic ignition unit heater and contains
the burner controls, the electrical terminal box for the system, the control relays for the operation of
the heater/cooling equipment, and the transition piece between the heater and the fan compartment.
The heater is an open flued gas fired heater of flue type B
11
for vertical flue.
The On/Off heaters are Cat II
2H3+
appliances for use with Natural Gas or L.P.G. as stated on the
heater data plate (Modulating and High/Low burners are Cat I
2H
for use with Natural Gas only), and
are intended for indoor installation only. They must be installed and commissioned in accordance
with local regulations and the requirements of Section 3 of these Instructions.
A permanent electrical supply of 400 volts 50 Hz, three phase and Neutral is required for the operation
of the heater and fan and all models must be earthed. (Note the burner operates on 230v 50 Hz taken
internally from the above supply).
1.1.4
Fan Section
The fan section houses the double-inlet, belt-drive centrifugal blower fan and three phase electric
motor. This section of the cabinet is fully insulated with foil faced glass fibre insulation.
The fan rotation is counter clockwise viewed from the control side as marked on the fan case.
1.1.5
Cooling Coil
DualAir® units can be fitted with either a DX or Chilled Water cooling coil:
1.1.5.1
DX Coil
The DX cooling coil is installed into the DualAir® unit with the two refrigerant circuits sealed ready for
site connection. There are no other refrigerant controls supplied with the coil and all refrigerant pipe-
work and controls must be supplied by the installer to suit the equipment being installed with the
condenser units.
DX coils are designed for operation at an ambient temperature of 28°C using R22 or R407C refrigerant
evaporating at 6°C.
The installation of the cooling condensers and the refrigerant circuits must be carried out in accordance
with the condenser manufacturers instructions.
Summary of Contents for Dualair DA260G Series
Page 2: ...Details of condense drain for cooling coil ...
Page 9: ...Page 7 Fig 2 2 DualAir 380 Module Dimensions FRONT VIEW REAR VIEW SIDE VIEW ...
Page 34: ...Page 32 Fig 5 2 Wiring for DualAir Units On Off Burner 24v Controls ...
Page 35: ...Page 33 Fig 5 3 Wiring for DualAir Units Hi Low Burner 230v Controls ...
Page 36: ...Page 34 Fig 5 4 Wiring for DualAir Units Hi Low Burner 24v Controls ...
Page 37: ...Page 35 Fig 5 6 Wiring for DualAir Units BMS Burner Modulation 230v Controls ...
Page 38: ...Page 36 Fig 5 7 Wiring for DualAir Units BMS Burner Modulation 24v Controls ...
Page 39: ...Page 37 Fig 5 7 Wiring for DualAir Units Full Burner Modulation 230v Controls ...
Page 40: ...Page 38 Fig 5 8 Wiring for DualAir Units Full Burner Modulation 24v Controls ...
Page 41: ......
Page 42: ......
Page 43: ......
Page 44: ......
Page 45: ......
Page 46: ......
Page 47: ......
Page 48: ......
Page 49: ......
Page 50: ......