The arc sensor can be mounted from the outside on partition wall of the switchgear. The active
part of the sensor is mounted in a 10mm hole, to the area in the switchgear that should be
protected, and fastened with a 4mm self-tapping screw.
Switchgear
panel
2 x M4
self threading
mounting screws
(Supplied)
Sealed cable
stress relief
Optical detector
protruding through
hole in panel
1S30 shown mounted on the outside of a switchgear panel
Detector oriented to ‘look’ through a 10mm diameter hole into the switchgear
Refer to panel cut out drawing in 1S30 Technical Bulletin for details.
The arc sensor can alternatively be mounted completely in the protected area with the help of a
Z-shaped or L-shaped mounting plate. In open spaces, such as the bus bar section, arc sensors
should be mounted a maximum of four meters apart.
In open spaces (e.g. bus bar sections) there should be an arc sensor approximately every 5
meters. Due to the wide detection range of the sensors and the light reflection inside the
switchgear, the mounting position is not very critical.
SENSOR LOCATIONS
SENSOR LOCATIONS