USE 09 MEASURED VALUES AND PARAMETERS
...............................................................................................................................................................................................................
...............................................................................................................................................................................................................
Manual USZ 08 · EN05 · 2015-06
51
AK (...AR)-21 A p# blanking count
tic
2540
L Path# blanking count
AK (...AR)-22 E path-# decay time
ms
1120
F Path# decay time at the end of measurement
AK (...AR)-23 E path-# path length
mm
1140
F Path# length of path
AK (...AR)-24 E path-# axial dist.
mm
1160
F Path# min. axial distance of path
AK (...AR)-25 E p# assembly angle
°
1500
F Path# assembly angle of the sensor
AK (...AR)-26 E p# delta-t offset
us
1420
F Path# time difference offset
AK (...AR)-27 E const-K# d.1
[1]
1200
F Path# constant K# direction 1
AK (...AR)-28 E const-K# d.2
[1]
1220
F Path# constant K# direction 2
AK (...AR)-29 E const w#
[1]
1240
F Path# constant w#
AK (...AR)-30 E p# tic offset
tic
2200
I Path# Tic offset
AK (...AR)-31 E p# tic offset (X)
tic
2260
I Path# Tic offset (3X measurement)
AK (...AR)-32 E p# AGC-limit
dB
2220
I Path# AGC error limit
AK (...AR)-34 C P# no. of f-batches
2312
I Path# number of measurements (FBatches)
Note:
The Modbus addresses stated are for path 1! To determine the Modbus addresses for the
other paths, see chapter "Brief description of the USE09 Modbus".
Service
Value
Unit
Modbus
Description
AS-01 E CPU speed
Hz
2574
L Actual M32 clock speed
AS-02 E DSP speed
Hz
2576
L Actual DSP clock speed
AS-04 E FPGA speed
Hz
2578
L Actual FPGA clock speed
AS-05 E ext. card s.no.
2584
L IO card s. No.
AS-06 E ext. ADC s.no.
2586
L IO-ADC card s. No.
AS-07 E write opt.EEProm
2167
M (Service key!) Writes parameters in the OPT-EEP (
NO
, YES)
AS-08 E write ADC EEProm
2168
M (Service key!) Writes parameters in the OPT-ADC-EEP (
NO
, YES)
AS-09 N LCD lighting
2183
M Display lighting if key is pressed or steady light (
KEY
, ALWAYS)
AS-10 Z parameter reset
2148
M Load new parameters (
NO
, YES)
AS-12 C def. val. reset
2149
M Reset default values (
NO
, YES)
AS-13 C RV: number
2150
I Number of mean values used to calculate the replacement values
AS-14 A RV status
720
T Indication of the replacement value status
AS-15 C def. val. mode
2213
M Operating mode of default values (OFF,
ON
)
AS-16 N Raw data path no.
2124
I Raw data: Path selection (0=OFF)
AS-17 N Raw data type
2184
M Raw data: Type selection (TEST,
RAW
, FILTER, RAW_ERR,
FILTER_ERR, FFG, ROH_FFT, FILTER_FFT)
AS-18 N Raw data function
2215
I Raw data: Trigger function (subselection)
AS-20 A M32 temperature
°C
5000
F Temperature of the M32 board
AS-21 A transmit level
%
5002
F Transmission level HV analog board
AS-22 A +-5V symmetry
V
5004
F Sy-5V, analog board
AS-23 A system temperature
°C
5006
F Temperature, baseboard
AS-24 A +-12V symmetry
V
5008
F Sy-12V, analog board
AS-25 A 1V2 voltage
V
5010
F Voltage 1V2 DSP board
AS-26 A 1V5 voltage
V
5012
F Voltage 1V5 DSP board
AS-27 A 3V3 voltage
V
5014
F Voltage 3V3 M32 board