Specifications
44
Operating Instructions for the TERZ 94 Electronic Turbine Meter
LF output
In the case of the explosion-protected (Ex) design, the device can only be
connected to a certified intrinsically safe circuit. (For Ex connected loads, see
approval certificate.)
Terminals: X4,2
(+)
X4,1
(-)
Output: Open-drain
transistor
T
pulse
125
ms ± 10% (F
max
: 4 Hz)
250 ms ± 10% (F
max
: 2 Hz)
Ex
Non-Ex
U
min
:
4.0 V
4.0 V
U
max
:
28 V
30 V
I
max
:
60 mA* (total current)
400 mA
External inductance
1 H
External capacitance
25 µF
* maximum total current of the 3 pulse outputs (LF + HF + Alarm)
Alarm output
In the case of the explosion-protected (Ex) design, the device can only be
connected to a certified intrinsically safe circuit. (For Ex connected loads, see
approval certificate.)
Terminals: X4,6
(+)
X4,5
(-)
Output: Open-drain
transistor
Ex
Non-Ex
U
min
:
4.0 V
4.0 V
U
max
:
28 V
30 V
I
max
:
60 mA* (total current)
400 mA
External inductance
1 H
External capacitance
25 µF
* maximum total current of the 3 pulse outputs (LF + HF + Alarm)
Summary of Contents for TERZ 94
Page 2: ......
Page 11: ...Safety Instructions Operating Instructions for the TERZ 94 Electronic Turbine Meter 9...
Page 21: ...Installation Operating Instructions for the TERZ 94 Electronic Turbine Meter 19...
Page 23: ...Installation Operating Instructions for the TERZ 94 Electronic Turbine Meter 21...
Page 35: ...Operation Operating Instructions for the TERZ 94 Electronic Turbine Meter 33 3 Test protocol...
Page 62: ...Annex 60 Operating Instructions for the TERZ 94 Electronic Turbine Meter mode are blanked out...