- 19 -
4-7. Changing the alarm setpoint
In the detector, the alarm setpoint is factory set to 30 ppm. The detector has 5 preset alarm setpoints that
the user can cycle through (10 ppm, 30 ppm, 150 ppm, 500 ppm, and 2000 ppm).
How to change the alarm setpoint
1 In the detection mode, press the AIR and MODE buttons at the same time.
The alarm setpoint is changed to the next pre-defined setpoint every time the AIR and MODE buttons
are pressed. There are 5 setpoints total, all in the ppm range.
NOTE
•
The alarm setpoint cannot be set to 10000 ppm.