35-3001A-01-XX1 Sample-Draw Detector Operator’s Manual • 13
Figure 4: Outline and Mounting Dimensions
2. Close and latch the housing door.
NOTE:
The sample-draw detector is shipped with the mounting feet “tucked under” the
housing to protect the mounting feet during shipment.
3. Slightly loosen the screw that secures the mounting foot to the housing, then rotate the
mounting foot 180 degrees (see Figure 4).
4. Tighten the screw that secures the mounting foot to the housing.
5. Repeat steps 3 and 4 for the remaining three mounting feet.
6. Position the sample-draw housing on a vertical surface at eye level (4 1/2 to 5 feet from
the floor).
7. Insert 1/4 inch screws through the slots in the mounting feet to secure the housing to the
mounting surface.