2. COMMUNICATION IDENTIFIER LIST
IMSRM07-E6
29
Positioning adjustment counter (H-TIO-K module)
Item
Setting data
(Setting
counter
value)
Description
Status
0
Normal status
Opening
adjustment
1
Opening adjustment star, open-side output start
(Motor time: 110 %)
Automatic
2
Capture the open-side opening value after 3 seconds
stop
3
Close-side output start (Motor time: 110 %)
4
Capture the close-side opening value after 3 seconds
stop
5
Above data stored in H-TIO-K module
6
Hold status
Capture the
motor time
7
Outputs the close-side until the positioning becomes
0 %.
Open-side output start if the positioning is less than
0 %.
Stops at an positioning of more than 100 %, and
capture the motor time by H-TIO-K module
Automatic
8
After the motor time has been captured, close-side
output comes ON (Motor time: 110 %)
9
Hold status
−
10 to 100
Not settable
When you input setting counter 1, the opening adjustment starts, operations are carried out
automatically up to setting counter 6, then the system goes on hold status. When you input setting
counter 7, the motor time capture starts, operations are carried out automatically up to setting counter
9, then the system goes on hold status. After the settings are complete, always set to “0: Normal
status.”