1. TRANSFER TO INITIAL SETTING
IMSRM07-E6
2
Transfer to Initial setting mode
Transfer to Extended communication (Initial setting mode) sets in “1” with identifier IN (Initial setting
mode of normally communication).
The control unit cannot be switched to the Extended communication (Initialize setting
mode) state at control start (during control). If it needs to be switched to the above state,
first stop the control by “Control RUN/STOP transfer (Identifier: SR).”
No control can be started during Extended communication (Initialize setting mode).
If the control needs to be re-started, first switch the control unit the normal
communication (Set the identifier IN to 0) state.
[
Normally communication
]
Name
Iden-
tifier
Digits
Attri-
bute
Struc-
ture
Data range
Factory
set
value
Control RUN/STOP
transfer
[
-PCP-A/B]
SR
1
R/W
U
0: Control STOP
1: Control RUN
Only when the initial set
mode is “0: Normal
communication,” control can
be start.
0
Initial setting mode
[
-PCP-A/B]
IN
1
R/W
U
0: Normal communication
Normal communication is
possible.
1: Extended communication
(Initialize setting mode) *
Normal and initial setting
communication are
possible.
0
R/W: Read and Write U: Data for each unit address
*
If Extended communication (Initialize setting mode) is selected, the communication data of the
Extended communication (Initialize setting mode) can be changed or selected.
For normally communication, refer to the
SR Mini HG SYSTEM Communication Quick
Manual (IMS01V02-E
)
or
SR Mini SYSTEM Communication Instruction Manual
(IMSRM04-E
)
.