2. COMMUNICATION IDENTIFIER LIST
IMSRM07-E6
7
Continued from the previous page.
Name
Iden-
tifier
Digits
Attri-
bute
Struc-
ture
Data range
Factory
set value
ON/OFF control
differential gap (lower)
[
-TIO-
, H-CIO-A]
IW
6
R/W
C
0.00 to 10.00
%
of span
0.02
Manipulated output
value at input error
[
-TIO-
, H-CIO-A]
OE
6
R/W
C
−
5.0 to
+
105.0 %
(Heat control, Position
proportioning control)
−
105.0 to
+
105.0 %
(Heat/Cool control)
0.0
Output change rate
limiter (up)
[
-TIO-
, H-CIO-A]
PH
6
R/W
C
0.0 to 100.0 %/second
(0.0: OFF)
Setting will be invalid in
ON/OFF control.
For details, refer to
Output
change rate limiter (P. 21)
.
0.0
Output change rate
limiter (down)
[
-TIO-
, H-CIO-A]
PL
6
R/W
C
0.0 to 100.0 %/second
(0.0: OFF)
Setting will be invalid in
ON/OFF control.
For details, refer to
Output
change rate limiter (P. 21)
.
0.0
Direct/Reverse action
selection
[
-TIO-
, H-CIO-A]
XE
1
R/W
C
0: Direct action
1: Reverse action
If the forward operation/reverse
operation selection is changed,
all set values of the
corresponding module will be
changed (initialized).
Setting will be invalid in
Heat/Cool control.
Depends on
model code
Hot/Cold start selection
[
-TIO-
, H-CIO-A]
XN
1
R/W
C
0: Hot start
At restarting
Operation mode
→
Same as mode before the
power failure
Output value
→
Same as value before the
power failure
1: Cold start
At restarting
Operation mode
→
Same as mode before the
power failure
Output value
→
Output limiter low
1
Continued on the next page.