2. COMMUNICATION IDENTIFIER LIST
IMSRM07-E6
23
Digital input (DI) of H-DI-A module
The types below can be selected for the digital input (DI) of the H-DI-A module.
Function mode 1:
−
Memory area transfer (ENABLE terminal is used)
After area selection setting, the actual area is changed by detecting the ENABLE edge.
−
Control RUN/STOP transfer
−
Alarm interlock release
Function mode 2:
−
Memory area transfer
The actual area is changed approximately 2 seconds after area selection setting.
−
Control RUN/STOP transfer
−
Alarm interlock release
After the contact is closed, it takes a short time until the action of this device is actually
selected. Therefore, pay attention to this delay time if the device is used together with a
PLC, etc.
Memory area selection, Control RUN/STOP selection and Alarm interlock release
Selection or release can be performed depending on the open or closed state of terminal numbers 1 to 8.
For memory area selection, configure an external contact circuit or use a contact output signal from the
PLC, if necessary.
Control area
Terminal No.
1
2
3
4
5
6
7
8
1 - 2
−
×
−
×
−
×
−
×
1 - 3
−
−
×
×
−
−
×
×
1 - 4
−
−
−
−
×
×
×
×
−
: Open
×
: Closed
When in function mode 1:
The memory area (control area) is established by closing terminal number 5
(ENABLE terminal).
Connect external power (24V DC) to the number 1 and number 6 COM (common) terminals
on the DI module so that these terminal sides become positive (+).
Unused
Control RUN/STOP selection (contact closed: RUN, contact open: STOP)
-
-
1
2
3
4
5
6
7
8
9
10
(COM)
(COM)
+
+
(1)
(2)
(4)
SET
DI1
DI2
DI3
DI4
DI5
DI6
DI7
DI8
Alarm interlock release (contact closed: Alarm interlock release)
(No alarm interlock function is activated if the contact is in the normally
closed state.)