6. REMOTE INPUT/OUTPUT AND REMOTE REGISTERS
IMSRM52-E4
53
Extension No. for setting selection processing
The content of the extended setting remote register is selected and the set value is changed.
AT start procedure (Example of CH1)
Instructs AT execution.
Cautions when selecting the memory area
When selecting the memory area, two seconds are required to update data items such as set values
(SV) and PID constants. Read the above data items after a lapse of more than two seconds.
Extension No. for setting
[RYn6 to RYnB]
Extended setting flag
[RYnD]
Extended setting
completion [RXnD]
Remote register
[RWwm to RWwm+F]
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Data usage
Data usage
Remote register [RWwn]
(Extension No. 4:
PID/AT transfer)
Extended setting flag
[RYnD]
Extended setting
completion [RXnD]
AT setting status
PID/AT transfer status
[RXn4]
Data = 1
Data = 0
ON
OFF
ON
OFF
ON
OFF
ON
OFF
2
sec.