6. REMOTE INPUT/OUTPUT AND REMOTE REGISTERS
IMSRM52-E4
47
Continued from the previous page.
Name
Attri-
bute
Data range
Description
Factory
set value
20
Manual output value
R/W
−
5.0 to
+
105.0 %
Sets the manual output
value.
0.0
21
Cannot be used.
−
−
−
−
22
Cannot be used.
−
−
−
−
23
Cannot be used.
−
−
−
−
24
Heater break alarm
(HBA) set value *
R/W 0 to 30.0 A:
CTL-6 type
0.0 to 100.0 A:
CTL-12 type
Sets the heater break
alarm set value for the
CT input of the H-CT-A
module.
0.0
25
Decimal-point
position
RO
0: No decimal point
1: 1 digit below
decimal point
2: 2 digits below
decimal point
3: 3 digits below
decimal point
Displays the position of
the decimal point of the
temperature measured
value, temperature set
value and alarm set value.
−
26
Manipulated output
(Cool-side)
RO
−
5.0 to
+
105.0 %
Displays the manipulated
output on the cool-side.
−
27
Proportional band
(Cool-side)
R/W 0.1 to 1000.0 % of
span
Sets the proportional band
(cool-side) in heat/cool
PID control.
3.0
28
Proportioning cycle
time (Cool-side)
R/W 1 to 100 seconds
Sets the proportioning
cycle time (cool-side) in
heat/cool PID control.
Setting will be invalid
with output of
current/voltage and heat
action.
20
a
29
Overlap/Deadband R/W
−
10.0 to
+
10.0 % of
span
Sets the control deadband
between proportional
bands (heat-side and
cool-side) in heat/cool
PID control. Overlapped
if minus (
−
) is set.
0.0
* For details of the heater beak alarm function, see page 50.
a
Relay contact output: 20 seconds
Voltage pulse output, open collector output, triac output: 2 seconds
For current/voltage output: Setting is ineffective.
Continued on the next page.