8. HOST COMMUNICATION
IMSRM52-E4
65
List of remote register (4 stations occupied, Temperature control 8 channels)
If “1: 8 Channels” is selected by the number of
Control & Communication Link
occupying channels
(ZC), the content of the remote register becomes as follows.
For details on the remote register when “0: 16 channels” is not changed prior to factor shipment, see
6.3 Remote Registers (P. 43)
.
“
n
” and “
m
” in the table are the addresses assigned to the master station by the station No.
setting. They can be calculated by the following equations:
n = (Station No.
−
1)
×
4
m = (Station No.
−
1)
×
4
As the calculation results are expressed in decimal digits, they are converted to hexadecimal
digits before substituted for “
n
” and “
m
” in the table.
Example: If the station No. of the H-LNK-A module is “1” or “5”
For station No. 1: Remote register RWrn to RWrn+F
→
RWr0 to RWrF
RWwm to RWwm+F
→
RWw0 to RWwF
For station No. 5: Remote register RWrn to RWrn+F
→
RWr10 to RWr1F
RWwm to RWwm+F
→
RWw10 to RWw1F
Direction: Remote device station (Temperature control unit)
→
Master station (PLC)
[RWr]
Address Details
RWrn
CH1 Temperature measured value (PV)
RWrn+1
CH2 Temperature measured value (PV)
RWrn+2
CH3 Temperature measured value (PV)
RWrn+3
CH4 Temperature measured value (PV)
RWrn+4
CH5 Temperature measured value (PV)
RWrn+5
CH6 Temperature measured value (PV)
RWrn+6
CH7 Temperature measured value (PV)
RWrn+7
CH8 Temperature measured value (PV)
RWrn+8
CH1
RWrn+9
CH2
RWrn+A
CH3 Data specified by the Extension No. setting for display [RYn0 to RYn5]
*
RWrn+B
CH4 For details of the Extension No. and data, see
6.4 Extension No. (P. 45)
.
RWrn+C
CH5
RWrn+D
CH6
RWrn+E
CH7
RWrn+F
CH8
For details, see page 66.