![RKC INSTRUMENT CB100 Series Connection Manual Download Page 208](http://html.mh-extra.com/html/rkc-instrument/cb100-series/cb100-series_connection-manual_1466586208.webp)
Temperature Controller Driver
GP-Pro EX Device/PLC Connection Manual
208
15H)
•
1:1 Connection
•
1:n Connection
• The 5V output (Pin #6) on the Display is the power for the Siemens AG’s PROFIBUS
connector. Do not use it for other devices.
• We recommend the TM4P-66P from HIROSE ELECTRIC CO., LTD. as the modular
connector.
• To use the External Device's COM.PORT, pair COM.PORT1 with COM.PORT2, and
COM.PORT3 with COM.PORT4.
• In COM on the GP-4107, the SG and FG terminals are isolated.
2
1
T/R(B)
T/R(A)
3
SG
120
Ω
(1/2W)
Display
Shield
COM.PORT1
or COM.PORT3
modular connector
Terminal block
External Device side
Signal name
Pin
External
Device
Termination
resistance
Connect the terminating
resistor connector
W-BW-01 for Z-COM
to COM.PORT2
or COM.PORT4.
Pin
Signal name
NC
NC
GND(SG)
RS(RTS)
5V
NC
NC
FG
LINE(+)
LINE(-)
3
8
1
2
5
4
6
7
9
Shell
Display side
D-Sub 9pin (plug)
2
1
T/R(B)
T/R(A)
3
SG
120
Ω
(1/2W)
W-BF-02
Display
Shield
COM.PORT1
or COM.PORT3
modular connector
Terminal block
External Device side
Signal name
Pin
COM.PORT2
or
COM.PORT4
External
Device
COM.PORT1
or
COM.PORT3
External
Device
Termination
resistance
Connect the terminating
resistor connector
W-BW-01 for Z-COM
to COM.PORT2
or COM.PORT4.
Pin
Signal name
NC
NC
GND(SG)
RS(RTS)
5V
NC
NC
FG
LINE(+)
LINE(-)
3
8
1
2
5
4
6
7
9
Shell
Display side
D-Sub 9pin (plug)