Unit does not burn properly
1. Check the wood; it must be dry. If
moisture is sizzling out the end, the wood
is too wet.
2. Test the draft. It should be .05/.06
(inches of water column).
3. Check to make sure the flue is not
obstructed. Also, check the baffle area in
the unit for excessive ash buildup.
4. Check the ash drawer. Empty the
drawer if it has too much ash in it.
Combustion air needs to come up
through the grates on Energy King
heating appliances to feed the fire.
5. Check the airflow in the room. If it is too
airtight, the unit cannot get enough
combustion air to burn properly. You may
need to bring outside air to the furnace or
stove.
6. Check the chimney and stovepipe. They
need to be airtight to make the unit draft
properly.
7. Check that only one appliance is hooked
to the chimney.
8. Check the chimney for a downdraft. A
cold chimney will keep flue gases from
rising up the chimney. Proper insulation
of the chimney and/or installing a
stainless steel liner sized for the unit may
remedy the problem.
9. Check your chimney for downdraft
caused by taller surrounding trees or
buildings. The chimney may have to be
extended or a chimney vent cap
installed.
10. Check all gaskets for leaks: Door
gaskets, glass gaskets, ash drawer or
door gaskets (where applicable).
Unit does not give off enough heat
Is the unit installed correctly?
1. Check to see if the unit has an adequate
cold air return or inadequate hot air
outlet.
2. Furnace room may be too airtight,
inadequate combustion air or return air.
3. Flue draft may be inadequate or too
strong - .05/.06 (inches of water column)
recommended.
4. Door gaskets may be leaking. In
addition, glass gaskets, ash drawers or
door gasket should be checked for
leakage.
5. Check flue. Make sure it is not
obstructed.
6. Check ductwork for leaks, cold and hot
air ducts.
Unit is making noise/distribution
blower is vibrating
With electrical power disconnected,
check the following:
1. Check for loose parts.
2. Is the blower wheel contacting the
housing? If so, realign or replace as
required.
3. Is foreign material inside the housing?
4. Is there a leak in the ductwork or is there
loose ductwork?
5. Does the blower wheel/motor need to be
cleaned or serviced?
6. Is the blower wheel set screw loose? If
so, secure it properly.
Maintenance of blower assembly
After disconnecting the power source,
a) Remove dirt from blower wheel and
housing.
b) Check tightness of wheel set screw.
c) Check the wiring to see if it is secure
and well insulated.
d) Lubricate the motor according to the
manufacturer’s instructions. Remove
any excess lubricants.
Troubleshooting Guide
17
Summary of Contents for ENERGY KING 360EK
Page 11: ...Wiring Diagram Auto Draft 8...
Page 12: ...9 9...
Page 13: ...Wiring Diagram Manual Draft 10...