Stovepipe Installation 

 

 

When burning coal, a Barometric Draft 
Damper must be installed at a safe, 
convenient place between the chimney and 
your Energy King. Setting at .06

 W.C. 

C

AUTION

 

D

O NOT INSTALL THE 

E

NERGY 

K

ING WARM AIR 

SUPPLY INTO THE COLD AIR RETURN OF THE 

CENTRAL FURNACE

.

 

T

HE COMPONENTS OF THE 

CENTRAL AIR FURNACE COULD OVERHEAT

 
Install your wood/coal unit as close to the 
chimney as possible with a minimum of 
elbows (no more than two are  
recommended) and a run of no more than 6 
feet horizontally. The pipe should maintain a  
½ inch rise per linear foot and 

never

 be 

installed closer than 18 inches from 
combustibles. Exceeding these 
recommendations normally results in  
creosote buildup, a smoking furnace or one 
with a poor draft. 
 
When connecting stovepipe, all joints should 
be secured with at least three sheet metal 
screws. If it is absolutely necessary to have a 
run of more than 6 feet (which is not 
recommended), use extra support hangers or 
brackets every 3 feet. 
 
The connection to the wood burner’s collar 
must also be more than just a snug fit and 
secured with sheet metal screws. Mark each 
connection for cleaning. This will prevent 
frustration when matching up your hole pattern 
again. 
 

Dampers in Stovepipes.  

Put a manual 

damper at a safe, convenient place between 
the chimney and your Energy King furnace.   
In case of a chimney fire, it can quickly be 
closed reducing draft to the chimney. Keep  
the manual damper completely open during 
normal operation. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Barometric Draft Installation 

 
Some codes and the NFPA require draft 
regulators in the chimney connector of wood 
or coal furnaces and boilers. 
 

Draft regulators limit the draft (the suction 
pulling air into the appliance). A pivoted, 
counterbalanced flap is pulled open by the 
draft when the draft reaches a critical  
amount. This permits air to enter the  
chimney, thus preventing the draft in the 
appliance from rising any higher. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Air Duct Installation 

 
The ducts, fittings and registers should be 
sized so that the total external static pressure 
does not exceed 0.2. 
 
The plenum on the Energy King 480EK  
should be 20

 x 20

 and on the Energy King 

360EK the plenum should be 18

 x 18

. The 

plenum should be no closer than 2 inches 
from the ceiling or any combustible material.  
In a power outage situation, excessive heat 
buildup in the plenum top may be dangerous; 
so make sure clearances are maintained. 

NEVER

 supply less than 150-square inches  

of constant heated air outlet area. 
 
 
 
 
 
 
 
 
Cold air returns must be equal in size to the 
heated air outlets and preferably 10% larger. 
Every Energy King furnace 

MUST

 be  

installed with a cold air return. 

 

12

Summary of Contents for ENERGY KING 360EK

Page 1: ...Wood or Coal Furnaces Models 360EK and 480EK Installation Operation Maintenance Manual RJM Manufacturing Inc PO Box 27 1875 Olson Drive Chippewa Falls WI 54729 715 720 1794 Fax 715 720 1797...

Page 2: ...he installation must be performed by a qualified installer With proper installation and maintenance your Furnace will give you years of trouble free service Energy King s Furnace is designed to burn A...

Page 3: ...ng Diagram Forced Draft 9 Wiring Diagram Manual Draft 10 Filter Box Assembly Schematic 11 STOVEPIPE INSTALLATION 12 BAROMETRIC DRAFT INSTALLATION 12 AIR DUCT INSTALLATION 12 OPERATION 13 GENERAL INSTR...

Page 4: ...ill cause safety and operation problems 8 Do not connect your solid fuel appliance to a chimney flue already venting another appliance 9 Do not let an accumulation of either soot or creosote build up...

Page 5: ...022 98 Cast Iron Hearth End Plates 2 EK007 98 Ash Pan removable EK023 98 Shroud Top EK008 98 Self Tapping Bolts 3 EK024 98 Shroud Left Side EK009 98 x Bolts 8 EK025 98 Shroud Right Side EK010 98 Nuts...

Page 6: ...ant step in positioning your wood coal furnace is the distance from your new or existing chimney The unit should be installed as close to the chimney as possible with a minimum of elbows no more than...

Page 7: ...is added A common mistake is to assume that sheet metal masonry or asbestos board placed directly against a wall protects it Materials installed in this manner give very little protection These materi...

Page 8: ...it and the supplemental unit must be compatible If all these conditions are met then the combined static pressure may not exceed that established by the existing furnace Once it has been determined th...

Page 9: ...mn All chimney connections must meet the approval of the local building inspector and fire marshall and conform to all local state and national codes It is also necessary to clean your chimney of creo...

Page 10: ...nters past any stops on the dial even though the dial may be graduated beyond the stops Limit Move the right hand pointer so that its straight edge indicates the temperature at which the contacts shou...

Page 11: ...Wiring Diagram Auto Draft 8...

Page 12: ...9 9...

Page 13: ...Wiring Diagram Manual Draft 10...

Page 14: ...Filter Box Assembly Schematic CAUTION THE FILTER MUST BE REMOVED IF THE FAN IS INOPERABLE FOR ANY REASON THIS WILL PREVENT OVERHEATING OF THE MOTOR THE AIR FILTER MUST BE NON COMBUSTIBLE 11...

Page 15: ...n Dampers in Stovepipes Put a manual damper at a safe convenient place between the chimney and your Energy King furnace In case of a chimney fire it can quickly be closed reducing draft to the chimney...

Page 16: ...weather Your automobile engine works effectively at 55 mph but can be damaged or destroyed at constant speeds of 90 mph Your furnace can be damaged if it is constantly fired at extremely high tempera...

Page 17: ...couple of handfuls of dry thick kindling wood then several small pieces of firewood Be sure the bypass damper is open 3 It will take 5 to 10 minutes for the fire to establish itself Once you have som...

Page 18: ...build up the coal bed 5 Allow your Energy King to operate with drafts on for approximately 15 minutes or until fresh coal ignites When the coal is properly ignited adjust the thermostat accordingly 6...

Page 19: ...ntly creosote residue accumulates on the flue lining When ignited this creosote makes an extremely hot hot fire The chimney connector and chimney should be inspected at least twice monthly during the...

Page 20: ...eaks Door gaskets glass gaskets ash drawer or door gaskets where applicable Unit does not give off enough heat Is the unit installed correctly 1 Check to see if the unit has an adequate cold air retur...

Page 21: ...n cause creosote buildup in smoke pipe and chimney Coal fire goes out or does not hold overnight Check for the following conditions 1 Poor draft 2 Incorrect damper settings 3 Improper firing methods f...

Page 22: ...ter preheating the chimney If hardwoods are unavailable you can control your fire s burn rate by using larger pieces of wood Q Is it important to season wood before burning it R The seasoning or dryin...

Page 23: ...hase All transportation charges on warranty appliances and appliance parts submitted for repair or replacement under this warranty shall be paid for the by purchaser field analysis of condition remova...

Reviews: