Product Manual | Lynx™ Shielded Dual‑Relay Output Module OR2‑M
RJG, Inc.
15
FUSE REPLACEMENT
Both relay contacts have replaceable fuses; a
spare fuse is supplied for each set of contacts,
located inside the OR2‑M module. Read and
follow all instructions, warnings, cautions, and
notes to replace a fuse with one of the spare
fuses.
REQUIREMENTS
The module must be removed from the
mounting location and any other hardware to
access the replaceable and spare fuses within
the module.
CAUTION
Always disconnect and lockout/
tag‑out any and all power before performing
maintenance on equipment. Failure to comply will
result in personal injury or death, and damage or
destruction of equipment.
TOOLS
•
Personal grounding strap
•
Phillips screw driver
•
Fuse puller
INSTRUCTIONS
1.
Remove two (2) 4‑40 x 3/8”
connector screws from the module’s
right side panel connector; remove
two (2) 4‑40 x 3/8” connector screws
from the module’s left side panel
connector; retain.
2.
Remove four (4) M3 x 8 mm panel
screws from the module’s right side
panel; retain.
3.
Remove the right side panel and EMI
gasket from the module; retain.