Make a template.
Place the cursor on the Cycle Graph slightly
before the machine pressure curve can be seen
dropping into hold.
Record the volume measurement from the
cursor. Open the V to
P Control tool from
the Options tab and select the check mark
next to the “Injection Volume Exceeds” field
to enable control; enter the recorded volume
measurement and select the correct units of
measure.
TESTING (
continued
)
The transfer point should be movable by
changing the volume number in the V to
P
Control tool. If the curve does not change
from the template (as shown below) then the
machine is not accepting the transfer signal from
the
eDART
.
The backup set points for time, position, or
pressure on the machine must be verified and
used during cavity pressure transfer control.
In the event that the cavity pressure transfer
control input is not detected by the machine
controller, the backup set points prevent
damage to the tool.