Rittal air/water heat exchanger assembly instructions
11 Further technical information
EN
11 Further technical information
11.1 Hydrological data
To avoid system damage and to ensure safe opera-
tion, Rittal GmbH & Co. KG recommends the use of
system water or an additive whose composition does
not differ from that presented in the following sum-
mary:
Tab. 7: Hydrological data
Hydrological data
Unit
Model No. SK
Model No. SK
1)
–
3209.100/3209.110/3209.140
3209.500/3209.510/3209.540
3210.100/3210.110/3210.140
3210.500/3210.510/3210.540
3209.104/3209.114/3209.144
3209.504/3209.514/3209.544
3210.104/3210.114/3210.144
3210.504/3210.514/3210.544
pH value
7 – 8.5
6 – 9
Calcium hardness
°dH
3 < 8
1 – 2
Free carbonic acid
mg/dm
3
8 – 15
1 – 100
Corresponding carbonic acid
mg/dm
3
8 – 15
Zero
Aggressive carbonic acid
mg/dm
3
0
0 – 400
Sulphides
mg/dm
3
Zero
Zero
Oxygen
mg/dm
3
< 10
< 10
Chloride ions
mg/dm
3
< 50
< 200
Sulphate ions
mg/dm
3
< 250
< 500
Nitrates and nitrites
mg/dm
3
< 10
< 100
COD
mg/dm
3
< 7
< 40
Ammonia
mg/dm
3
< 5
< 20
Iron
mg/dm
3
< 0.2
Zero
Manganese
mg/dm
3
< 0.2
Zero
Conductivity
µS/cm
< 2200
< 4000
Evaporation residue
mg/dm
3
< 500
< 2000
Potassium permanganate
mg/dm
3
< 25
< 40
Suspended matter
mg/dm
3
< 3
> 3 < 15: partial current purification recommended
> 15: continuous purification recommended
1)
The complete absence of corrosion under experimental conditions suggests that solutions with a significantly higher salt content
and greater corrosion potential (such as seawater) can still be tolerated.