Rittal air/water heat exchanger assembly instructions
7 Inspection and maintenance
EN
7
Inspection and maintenance
7.1 General
The air/water heat exchanger is a maintenance-free,
hermetically sealed system. The water circuit is
checked at the factory for leaks and subjected to a
function trial run.
The installed maintenance-free fan is mounted on
ball bearings, protected against moisture and dust,
and fitted with a temperature monitor. The life ex-
pectancy is at least 30,000 operating hours. The air/
water heat exchanger is consequently largely main-
tenance free. If dirt is present in the cooling water,
a filter must be fitted.
Maintenance interval: 2,000 operating hours.
Sequence of maintenance measures:
– Check the level of dirt.
– Cooling membranes soiled? Clean if necessary.
– Activate test mode; cooling function OK?
– Check the noise generation of the fan.
Fig. 22:
Disconnect the mains plug
Fig. 23:
Release the louvred grille
Fig. 24:
Remove the louvred grille
Fig. 25:
Disconnect the connector from the display
Risk of electric shock!
The unit is live.
Switch off the power supply before
opening, and take suitable precautions
against it being accidentally switched on
again.
Note!
Risk of fire!
Never use flammable liquids
for cleaning.