4 Assembly and connection
Rittal air/water heat exchanger assembly instructions
9
EN
Fig. 5:
Cover bungs
4.3 Assembling air/water heat exchangers
The enclosure air/water heat exchanger is fitted on
the roof of the enclosure.
To this end, the roof plate must be cut-out as per the
drilling template included with the supply.
4.3.1 Cutting out the enclosure
• Stick the supplied drilling template onto the roof of
the enclosure using adhesive tape.
There are dimensioning lines on the drilling template
to suit the installation type for your air/water heat ex-
changer.
• Make the cut-outs including the line width as
per the drilling template.
Deburr the cut-outs.
4.3.2 Assembling air/water heat exchangers
• Stick the supplied sealing frame onto the cut-out
roof plate.
Fig. 6:
Sealing frame on roof plate
• Mount the air/water heat exchanger on the
enclosure roof.
• Screw the supplied twin-threaded bolts into the
holes in the plastic base on the underside of the
device.
• Secure the unit using the supplied washers and
nuts.
Fig. 7:
Roof plate reinforcement for the TS 8 enclosure
Accessories for roof plate reinforcement with TS:
Punched rail
U nut
Fastening bracket
Threaded block
(refer also to Accessories in the Rittal Catalogue)
Note:
When using the cover bungs, no more than
2 cold air outlets should be sealed.
Note:
Pre-configured, reinforced roof plates
with cut-outs to match your enclosure are
available as accessories; refer to “System
climate control” in the Rittal Catalogue.
Risk of injury!
Carefully deburr all cut-outs to prevent
injuries caused by sharp edges.
Note:
In order to achieve a permanent seal be-
tween the
air/water heat exchanger
and the
enclosure, the mounting surface should be
reinforced or supported if necessary.
This is particularly applicable with large
roof areas.