6 Operation
Rittal air/water heat exchanger assembly instructions
25
EN
On the
master air/water heat exchanger
(00 = factory setting), set the number of slave units
present in the network:
01: Master with 1 slave
air/water heat exchangers
02: Master with 2 slave
air/water heat exchangers
03: Master with 3 slave
air/water heat exchangers
04: Master with 4 slave
air/water heat exchangers
05: Master with 5 slave
air/water heat exchangers
06: Master with 6 slave
air/water heat exchangers
07: Master with 7 slave
air/water heat exchangers
08: Master with 8 slave
air/water heat exchangers
09: Master with 9 slave
air/water heat exchangers
Fig. 21:
Master-slave connection (example)
For further connection examples, see “4.7.1 Bus
connection (only when interconnecting several units
with a Comfort controller)”, page 13.
For details of how to set the identifier, see “6.2.4 Ed-
itable parameters”, page 22 or “6.2.5 Programming
overview”, page 23, parameter “Ad”.
6.2.8 Evaluating system messages
In the Comfort controller, system messages are
indicated by a number in the display.
On the
slave air/water heat exchanger
(00 = factory setting), set its own address:
11: Slave
air/water heat exchanger
no. 1
12: Slave
air/water heat exchanger
no. 2
13: Slave
air/water heat exchanger
no. 3
14: Slave
air/water heat exchanger
no. 4
15: Slave
air/water heat exchanger
no. 5
16: Slave
air/water heat exchanger
no. 6
17: Slave
air/water heat exchanger
no. 7
18: Slave
air/water heat exchanger
no. 8
19: Slave
air/water heat exchanger
no. 9
Tab. 6: Troubleshooting with the Comfort controller
Master
02
Slave
11
Slave
12
Display
screen
System message
Possible cause
Measures to rectify the fault
A01
Enclosure door open
Door open or door limit switch incorrectly
positioned
Close door, position door limit switch correctly,
check connection if necessary
A02
Internal temperature of
enclosure too high
Cooling capacity inadequate/unit undersized Check cooling capacity
A08
Condensate warning
Condensate discharge kinked or blocked
Check condensate drainage; repair any kinks
or blockages in the hose
A10
Fan
Blocked or defective
Clear the blockage; replace if necessary
A16
Internal temperature sensor Open or short-circuit
Replace
A18
EPROM error
New board obstructed
Software update needed (only following board
installation with more recent software):
Enter the programming level with Code 22;
press button 1 and confirm with “Set” until
“Acc” appears. Next, disconnect the unit from
the mains and reconnect.
A19
LAN/Master-Slave
Master and slave not connected
Check setting and/or cable
A20
Voltage drop
Error display not shown
Event is stored in the log file
E0
Display message
Connection problem between the display
and the controller board
Reset: Switch power supply off, then switch on
again after approx. two seconds
Cable defective; connection loose
Exchange the boards