The radio signal strength between the signaling device and the 

security and fire alarm panel is determined by the level of signal 

attenuation which can be viewed in the configuration software, page 

Radio Device Map, upon connection to the panel.  

9.

 

Replacing Battery 

If necessary clean the bonding pads and replace the battery. During replacing the 

battery close the battery contacts for 2 seconds and then install the new battery

.

 

10.

 

Hardware Reset to Factory Settings 

Remove the battery from the holders, install the jumpers JMP1 + JMP3 and install 

the battery back. Figure 7.3 shows the procedure. 

11.

 

Device Installation 

Follow Code 5.13130.2009 during deployment and installation of signaling devices. 

1.

 

Locate and install signaling devices on the control object according to the 
premeditated project.  

2.

 

Install signaling devices on a wall surface at a hight of 1.4 - 1.6 meters from the 
ground or floor level to the control device and at a distance more than 1 meter 
from the radio channel receiver.  

 

Fig. 11.1. Fixing holes for signaling device 

3.

 

Do not install signaling devices at locations with possible gas, steam or aerosol 
emissions able to cause the corrosion. 

4.

 

Mark the signaling device location layout according to the figure 11.1. The figure 
5.1 (positions 2, 5) shows the mounting holes in the signaling device enclosure. 

5.

 

Remove the battery before mounting the signaling device enclosure base. 

6.

 

If the additional ribbon cable is used pull cables along the channel on the rear 
side of the enclosure base and connect them to the terminals of the connector 
XT1. 

7.

 

Lay loops of cable reserves next to terminal connectors so they do not prevent 
the installation and be fully covered by the enclosure. 

8.

 

Upon the enclosure installation install the battery, the front panel, screw holding 
screws in holes 1, 3, 4 (fig. 5.1) and reset the fire alarm button using the 
extractor. 

Summary of Contents for RIPR1

Page 1: ...Manual fire radio channel signaling device RIPR1 Data sheet Device identification number Firmware QA specialist Date of check Signature...

Page 2: ...essages low battery signal enclosure break in alarm Receiving these signals by the radio channel receiver RDK1 changes states of receiver outputs for a short time 2 sec Receiving a signal from the sig...

Page 3: ...mW max 10 Monitoring period of signaling device operation in radio system min 4 Dimensions mm 110 90 45 Weight g 160 Operating temperature range 40 55 Battery V 3 6 AA lithium battery Standalone opera...

Page 4: ...ders Respect polarity when installing battery XT1 Connector for alarm additional loop The loop type dry contacts Compatible with normally closed signaling devices without power supply by the loop If t...

Page 5: ...dio system t VD1 green Red Adding is in process The device is switched to the mode for adding to a radio system t The device is successfully added to the system An active device is found It is ready t...

Page 6: ...s up red for 4 seconds and then lights up green for 1 second If the depassivation has not been performed the red indicator lights up red for 2 seconds and then lights up green for 1 second The battery...

Page 7: ...wall surface at a hight of 1 4 1 6 meters from the ground or floor level to the control device and at a distance more than 1 meter from the radio channel receiver Fig 11 1 Fixing holes for signaling d...

Page 8: ...installation and maintenance activities applied to the device should be performed by duly qualified personnel 13 Transportation and Storage The device should be properly packed and transported in roo...

Reviews: