background image

 

 

JMP1 + JMP3 

Hardware configuration reset mode 

JMP3 

Radio channel test mode / standalone 

mode 

All jumpers removed 

Standby mode 

7.

 

Visual Indication 

Fig. 7.1. Standby mode  

t

Normal state

Alarm

green

green

green

 

Period 60 seconds

. . .

 

Red, 2 sec period – fire alarm
Red, 5 sec period – additional loop alarm
Red + green, 2 sec period – fire alarm + additional loop alarm

 

Fig. 7.2. Mode for adding to radio system 

t

VD1

green

Red

Adding is in process

The device is 

switched to the 

mode for adding 

to a radio system

t

The device is 

successfully added to 

the system

An active device is found. 

It is ready to add the 

signalling device

Blinks twice

Always on

 

Fig. 7.3. Hardw are configuration reset mode 

t

red

5 times

The sensor resetting settings

red

red

red

red

red

The settings have been reset

to factory settings

 

Fig. 7.4. Radio channel test mode

 

t

green

green

green

+

red

green

+

red

The sensor sent the test

message but got no answer

The sensor sent the test

message and got the answer

 

Summary of Contents for RIPR1

Page 1: ...Manual fire radio channel signaling device RIPR1 Data sheet Device identification number Firmware QA specialist Date of check Signature...

Page 2: ...essages low battery signal enclosure break in alarm Receiving these signals by the radio channel receiver RDK1 changes states of receiver outputs for a short time 2 sec Receiving a signal from the sig...

Page 3: ...mW max 10 Monitoring period of signaling device operation in radio system min 4 Dimensions mm 110 90 45 Weight g 160 Operating temperature range 40 55 Battery V 3 6 AA lithium battery Standalone opera...

Page 4: ...ders Respect polarity when installing battery XT1 Connector for alarm additional loop The loop type dry contacts Compatible with normally closed signaling devices without power supply by the loop If t...

Page 5: ...dio system t VD1 green Red Adding is in process The device is switched to the mode for adding to a radio system t The device is successfully added to the system An active device is found It is ready t...

Page 6: ...s up red for 4 seconds and then lights up green for 1 second If the depassivation has not been performed the red indicator lights up red for 2 seconds and then lights up green for 1 second The battery...

Page 7: ...wall surface at a hight of 1 4 1 6 meters from the ground or floor level to the control device and at a distance more than 1 meter from the radio channel receiver Fig 11 1 Fixing holes for signaling d...

Page 8: ...installation and maintenance activities applied to the device should be performed by duly qualified personnel 13 Transportation and Storage The device should be properly packed and transported in roo...