Reference conditions for Accuracy
Ambient temperature
23°C +/- 1°C
Pre-conditioning
30 min acc. to IEC EN - 60688
Input Variable
Rated Voltage
Input waveform
Sinusoidal, Form Factor 1.1107
Input signal frequency
50 or 60Hz
Auxiliary supply voltage
Rated Value
Auxiliary supply frequency Rated Value
Output Load
Rn = 7.5 V / Y2 ± 1%With
DC
current output signal.
Rn = Y2 / 1 mA ± 1% With DC
Voltage output signal.
Miscellaneous
Acc. to IEC EN - 60688
Additional Error
Temperature influence
±
0.2% /10°C
Influence of Variations:
As per IEC EN-60688
standard.
Output stability
< 30min
Safety
Protection
IP 40, housing acording to
IEC 60 529
IP 20,terminal according to
IEC 60 529
Pollution degree
2
Installation Category
III
56