rinnai new Zealand Limited
E-Frost Solar Collector Split System
install manual: 11497-a
10
Cylinder connections
Pressure
limiting valve
rinnai Glass Lined 180 litre
- 700 kPa
rinnai Glass Lined 270 and 340 litre
- 500 kPa
▪
▪
Cold water
pressure relief
valve
rinnai Glass Lined 180 litre
- 850 kPa approximately
rinnai Glass Lined 270 and 340 litre
- 700 kPa approximately
▪
▪
temperature
& pressure
relief valve
(tPr)
rinnai Glass Lined 180 litre
- 1000 kPa
[supplied with cylinder]
rinnai Glass Lined 270 and 340 litre
- 850 kPa
[supplied with cylinder]
▪
▪
Drain valve
Provision must be made to drain the cylinder if required for servicing.
Drain lines
These must be installed in accordance with aS3500 and or G12/aS1. G12 is
available online at no cost from:
www.dbh.govt.nz/building-code-compliance-documents
tempering
valve
during times of high solar gain water temperatures in solar systems can
become very high. a tempering valve will be required. Ensure that it is
suitable for use with solar systems. many suppliers have a dedicated solar
range to handle the higher temperatures.