Rinnai
8
Split AC IM
INDOOR UNIT
•
Ensure the indoor unit is located away
from heat or steam�
•
Ensure the indoor unit is located so it can
be accessed for service and replacement�
•
Ensure the indoor unit is located so
condensate can be drained away�
•
Select a location where the indoor unit
can be securely mounted�
•
The clearances shown
MUST BE
maintained�
OUTDOOR UNIT
•
Select the location where exposure
to direct sunlight and strong wind are
minimised�
•
Select the location where the outdoor unit
can be securely mounted�
•
Select the location where the noise and
air flow will not cause nuisance.
•
Ensure there are no obstructions in the
air flow path.
•
Ensure the out door unit is located so
it can be accessed for service and
replacement�
•
Do not place animals and plants near the
air discharge�
•
The clearances shown
MUST BE
maintained�
PIPE LENGTH & ELEVATION LIMITS
Models
Pipe Size
Standard
Length
Maximum
Length - X
Maximum
Height -Y
Additional
Refrigerant
Gas
Liquid
mm
inch
mm
inch
m
m
m
g/m
RINV25RC
Ø9.52
3/8
Ø6.35
1/4
5
15
8
20
RINV34RC
Ø9.52
3/8
Ø6.35
1/4
5
15
8
25
RINV51RC
Ø12.7
1/2
Ø6.35
1/4
5
20
10
30
RINV70RC
Ø15.88
5/8
Ø6.35
1/4
5
25
10
40
600
300
300
1000
100
100
2000
150
150
150
1000
(All dimensions in mm)
X
Y
Indoor unit
Outdoor unit
X
Y
Indoor unit
Outdoor unit
X
Y
Indoor unit
Outdoor unit
X
Y
Indoor unit
Outdoor unit
LOCATION