Maintenance Codes
55
Code
Definition
Remedy
16
Over temperature
warning (safety
shutdown because
unit is too hot).
Check for restrictions in air flow around the unit and vent termination.
Licensed
professional
only
Check for foreign materials in combustion chamber and/or exhaust piping.
Check for clogged heat exchanger.
Check that the gas type being used is correct for the unit.
30
FV sensor
(flammable vapor)
Licensed
professional
only
Check sensor wiring for damage.
Measure resistance of sensor.
Replace sensor.
31
Burner Sensor.
32
Heat exchanger
outgoing temp.
thermistor.
Licensed
professional
only
Check sensor wiring for damage.
Measure resistance of sensor.
Clean sensor of scale buildup.
Replace sensor.
35
Tank temperature
thermistor.
Licensed
professional
only
Check sensor wiring for damage.
Measure resistance of sensor.
Verify that sensor is properly mounted on the tank surface.
Replace sensor.
Summary of Contents for RH180
Page 1: ...Rinnai RH180 Hybrid Tank Tankless Water Heater Installation Fundamentals Level II 1...
Page 3: ...3 RH180 Hybrid Tank Tankless Water Heater Level II Training Program Installation Fundamentals...
Page 6: ...RH180 Sequence of Operation 6...
Page 8: ...RH180 Water Heater Sizing 8...
Page 10: ...RH180 Product Features Safety devices 10...
Page 18: ...Dimensions 18...
Page 38: ...RH180 Temperature Controller 38...
Page 39: ...Temperature Controller 39...
Page 41: ...RH180 Maintenance and Warranty 41...
Page 49: ...Component Description 49...
Page 50: ...Component Description 50...
Page 61: ...RH180 FAQ 61...