- 44 -
Issue 2 - 5/07/04 ©Rinnai
24. Gas Pressure Setting Procedure
Position gas selection switches to the correct position.
(see diagram opposite).
Remove pressure point screw and attach pressure
gauge.
Turn water ON.
Adjust pressure
1) Low
a. Position No. 2 of the bottom set of dip switches
to ON.
b. Remove the plug in the base of the appliance for
access to the regulator screw (modulating
valve).
Unlock screw and adjust to:
• Natural - 0.8 kPa
• Propane - 0.17 kPa
• LPG (NZ) - 0.15 kPa
c.
Lock regulator screw (modulating valve).
2) High
d. Position No. 3 of the bottom set of dip switches
to the ON position (leaving No.2 ON).
e. The HI potentiometer on the PCB, adjust the
pressure to:
Natural - 0.90 kPa
Propane - 2.26 kPa
LPG (NZ) 1.90 kPa
f.
Position switch No.2 and No.3 of the bottom set
of dip switches to the “OFF” position.
g. Turn water OFF. Replace plug in base.
h. Replace protective plastic cover over PCB.
Summary of Contents for REU-2018W
Page 8: ...Infinity REU 2425W 5 Issue 2 5 07 04 Rinnai 3 Dimensions Note All dimensions are in mm ...
Page 14: ...Infinity REU 2425W 11 Issue 2 5 07 04 Rinnai 7 Cut away Diagram ...
Page 15: ...Infinity REU 2425W 12 Issue 2 5 07 04 Rinnai 8 Schematic Diagram ...
Page 33: ...Infinity REU 2425W 30 Issue 2 5 07 04 Rinnai 20 Wiring Diagram ...
Page 54: ...Infinity REU 2425W 51 Issue 2 5 07 04 Rinnai 26 Exploded Diagram ...
Page 55: ...Infinity REU 2425W 52 Issue 2 5 07 04 Rinnai ...
Page 56: ...Infinity REU 2425W 53 Issue 2 5 07 04 Rinnai ...
Page 57: ...Infinity REU 2425W 54 Issue 2 5 07 04 Rinnai ...
Page 60: ...Infinity REU 2425W Issue 1 5 07 04 Rinnai Notes ...