Neo RIB2312 installation guide: 12148-A 01-17
|
33
Inbuilt mock chimney direct and offset flueing
500 mm min.* clearance from any
part of the building, refer p. 30
45 ° bend, maximum of
two per installation
Clearances from combustibles 10 mm (to allow
for contraction and expansion of the flue pipes)
Zero clearance box fitted,
must be installed flush with
the cladding surface to
ensure alignment of the flue.
M
inimum of 3
.6 m, maximum of 8 m
* The end of the flue shall be at least 500 mm from the nearest part of the chimney (AS/NZS 5601.1 6.9.2 (a))