Page 1: ...iHeat thermostat Installation guide TB7100A1000 MultiPROTM multispeed and multipurpose thermostat ...

Page 2: ...future reference Warning Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life For more information about buying living and servicing of Rin nai appliances call 0800 RINNAI 0800 746 624 Rinnai New Zealand Limited 105 Pavilion Drive Mangere Auckland PO Box 53177 Auckland Airport Auckland 2150 Phone 09 257 3800 Fax 09 257 3899 Em...

Page 3: ...contents General 4 Batteries wallplate date and time 5 Thermostat configuration 6 Installer thermostat tests 8 Troubleshooting table 10 ...

Page 4: ...cessed doorways etc hotspots direct sunlight above fireplaces heaters warm air ducts etc deadspots where air does not circulate freely alcoves corners behind doors etc Installing the thermostat Before installing the thermostat make sure the electrician has preinstalled the RJ45 cable 1 Take the thermostat out of the box and remove the wall plate from the face plate 2 Connect the adaptor provided t...

Page 5: ...wo ways to set the calendar and time for this thermostat setting date time when thermostat is first powered setting date time after thermostat is already functioning Setting date time when thermostat is first powered When the thermostat is first powered the display is ready to set the calendar and time The thermostat proceeds through a sequence of setup screens Setting date time after thermostat i...

Page 6: ...t Setup number Setting Default setting Settings available Notes 0120 Date year first two numbers 20 20 21 20 For years 20xx 21 For years 21xx 0130 Date year last two numbers 08 00 99 If you wanted the year 2015 you would use the up and down keys to display 15 0140 Date month 6 1 12 0150 Date day 15 1 31 For the 1st of the month to the 31st of a month 0160 Schedule options 4 0 non programmable Ther...

Page 7: ... arrow changes 4 fully locked Entire interface locked non functional 0680 Temperature control heat 2 1 less aggressive Set to 1 to reduce Infinity starts and allow room temperature to vary slightly 2 standard 3 more aggressive Set to 3 to control room temperature more but Infinity will start more often 0685 Recovery heat temp rate 5 0 20 F hour This parameter determines how quickly the room temp i...

Page 8: ...ured as a programmable schedule and when a fan is used The fan will run 1 3 hours before the occupied schedule starting time to circulate air Further information on temporary occupied duration limit 0535 While in programmable mode an override button is available to perform a temporary override In 0535 the override time can be limited 0 no limit 12 override limited to 12 hours Further information o...

Page 9: ...Rinnai iHeat thermostat Troubleshooting ...

Page 10: ...g is running Heating equipment is not operating Check wiring Check setup number 0170 and make sure 8 is selected Verify operation of equipment in system test mode Heat does not turn on Heating equipment failure Check for 24 Vac at the equipment on the secondary side of the transformer between power and common If voltage is not present check the heating equipment to find the cause of the problem Ch...