31
D. Solenoid Valves.
There are 3 solenoid valves and one modulating valve. Two of the solenoids are burner
sectional solenoids, and the third is the main, safety solenoid.
The easiest way to check the gas valve is by putting the manometer on the test point on
the gas valve and cycling the unit. If the solenoids are working correctly the burner
pressure when it lights should be around 8mbar. If the pressure stays at 0 mbar (or
goes up slightly, to about 1 mbar) the safety solenoid is not opening; this is only a true
test if the sparker is definitely sparking. If the pressure goes up to 21 mbar the sectional
solenoid is not opening. Once the suspect solenoid valve has been determined you can
determine the faulty component (solenoid valve or pcb.)
The solenoids should be tested for voltage and resistance at pcb connector F from the
wiring diagram. The resistance is measured with the unit electrically isolated and the
connector unplugged. Put the meter leads on the connections and measure through the
solenoid. The voltage is tested while the unit is running and the connections are made.
While the unit is lit put the leads into the plug and measure the voltage (DC.) Only the
Main SV and SV1 will open upon ignition. SV2 will not have voltage unless the unit is on
medium to high fire.
Main SV Pink – Black
200 – 240 Vdc
appx 6.5 k Ohms
SV1
Black – Blue
200 – 240 Vdc
appx 8.0 k Ohms
SV2
Black – Yellow
200 – 240 Vdc
appx 8.0 k Ohms
Modu SV Pink – Pink
2 – 15 Vdc
67 – 83 Ohms
If the voltage is incorrect replace the pcb.
If the resistance is incorrect replace the solenoid valve. It should be noted that
sometimes solenoids jam and are faulty even though the resistance is correct. If there is
voltage to it, and there is no gas getting past it, then it is a faulty solenoid, assuming you
have confirmed the incoming pressure. (High gas pressure will prevent a solenoid from
opening, for example, if a second stage LPG regulator has not been used.)
The voltage should be present after the spark ignitor has begun to tick. If the unit does
not begin to do anything check the Thermal Fuse Circuit (E.)
If the resistances and voltages are correct continue.
Check the secondary gas pressure change when the set temperature is changed from
55 to 37°C.
The secondary pressure should change. If it does, go to the water flow servo circuit (G.)
If the pressure does not change replace the modulating valve.
Diagnostic Checks
Summary of Contents for FUA-E
Page 1: ......
Page 5: ...5 Glossary of Terms and Symbols ...
Page 9: ...9 Dimensions ...
Page 11: ...11 Structure Diagram ...
Page 17: ...17 Gas Conversion Procedure ...
Page 18: ...18 Gas Conversion Procedure ...
Page 25: ...25 Operational Flow Chart ...
Page 26: ...26 Time Charts ...
Page 39: ...39 Diagnostic Checks Fault Finding Chart ...
Page 40: ...40 Fault Finding Chart ...
Page 41: ...41 Fault Finding Chart ...
Page 42: ...42 Fault Finding Chart ...
Page 43: ...43 Fault Finding Chart ...
Page 44: ...44 Fault Finding Chart ...
Page 45: ...45 Fault Finding Chart ...
Page 46: ...46 Wiring Diagram ...
Page 49: ...49 Dismantling for Service ...
Page 50: ...50 Dismantling for Service ...
Page 51: ...51 Dismantling for Service ...
Page 52: ...52 Dismantling for Service ...
Page 53: ...53 Dismantling for Service ...
Page 54: ...54 Dismantling for Service ...
Page 55: ...55 Dismantling for Service ...
Page 56: ...56 Exploded Diagram ...
Page 57: ...57 Exploded Diagram ...
Page 58: ...58 Exploded Diagram ...
Page 59: ...59 Exploded Diagram ...
Page 60: ...60 Exploded Diagram ...
Page 61: ...61 Parts List ...
Page 62: ...62 Parts List ...
Page 63: ...63 Parts List ...
Page 64: ...64 Parts List ...
Page 65: ...65 Letter of Compliance ...
Page 66: ...66 CE Certificate ...
Page 67: ......