Condensing Water Heater Service Manual
7
100000354
Code
Definition
Remedy
16
Over Temperature
Warning
Check for restrictions in the intake and exhaust system.
Check for low water flow in a circulating system causing short
-
cycling.
Check for foreign materials in combustion chamber and/or exhaust piping.
Check for blockage in the heat exchanger.
19
Electrical Grounding
Check all components for electrical short.
25
Condensate Trap Error
Condensate container is full.
Check condensate drain for blockage.
Replace condensate trap.
31
Burner Sensor Error
Measure resistance of sensor.
Replace sensor.
32
Outgoing Water
Temperature Sensor
Check sensor wiring for damage.
Measure resistance of sensor.
Clean sensor of scale build
-
up.
Replace sensor.
33
Heat Exchanger Outgoing
Temperature Sensor
Check sensor wiring to be sure it has not been short circuited.
Measure resistance of sensor.
Clean sensor of scale build
-
up.
Replace sensor.
41
Outside Temperature
Sensor
Check sensor wiring for damage.
Measure resistance of sensor.
Clean sensor of scale build
-
up.
Replace sensor.
51
Inlet Water Temperature
Sensor
Check sensor wiring for damage.
Measure resistance of sensor.
Clean sensor of scale build
-
up.
Replace sensor.
52
Modulating Solenoid
Valve Signal Abnormal
Check modulating gas solenoid valve wiring harness for loose or damaged terminals.
Measure resistance of valve coil.
57
Burner
(Bi
-
Metal sensors /
Thermal Fuse Harness)
Check for continuity through bi
-
metal sensors located at top of heat exchanger at white plastic
connector containing red an white wires.
58
Secondary Heat
Exchanger
There is scale build
-
up in the secondary heat exchanger and it needs to be flushed to prevent
damage. Refer to the flushing instructions in the manual. Hard water must be treated to prevent
scale build
-
up or damage to the heat exchanger.
61
Combustion Fan Failure
Ensure fan will turn freely.
Check wiring harness to motor for damaged and/or loose connections.
Measure resistance of motor winding.
Check for proper voltage from PC board.
65
Water Flow Control
The water flow control valve has failed to close during the bath fill function. Immediately turn off
the water and discontinue the bath fill function. Contact a state qualified or licensed contractor to
service the appliance.
70
Sensor Harness
Connection
Check PC board switches (in the bank of 6 switches, #2 should be on for indoor models and off for
outdoor models on KA series units only)
Check the connection harness at the E connection on the PC board. Outdoor models should have
2 orange cables at #7 and 8 positions. Indoor models should not have cables at these positions. If
this is incorrect then replace the sensor harness.
Replace PC board
71
Solenoid Valve Circuit
Replace PC board.
72
Flame Sensing Device
Verify flame rod is touching flame when unit fires.
Check all wiring to flame rod.
Remove flame rod and check for carbon build
-
up; clean with sand paper or emery cloth.
Check inside burner chamber for any foreign material blocking flame at flame rod.
Measure micro amp output of sensor circuit with flame present.
Replace flame rod.
Diagnostic Codes
Summary of Contents for Circ-Logic RU80e
Page 16: ...Condensing Water Heater Service Manual 16 100000354 KA Series Wiring Diagram RC80HPe RC80HPi ...
Page 17: ...Condensing Water Heater Service Manual 17 100000354 KA Series Wiring Diagram RC98HPe RC98HPi ...
Page 18: ...Condensing Water Heater Service Manual 18 100000354 KB Series Wiring Diagram RU80i e RU98i e ...
Page 57: ...Condensing Water Heater Service Manual 57 100000354 Notes ...
Page 58: ...Condensing Water Heater Service Manual 58 100000354 Notes ...
Page 59: ...Condensing Water Heater Service Manual 59 100000354 Notes ...